Phoenix MACX MCR-SL-2I-2I-ILP-SP-passive isolator 2905281, dual-channel input loop-powered 2-way isolator, using in-line connection technology, used for galvanic isolation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. In-line connection technology.

Product Type isolation amplifier
product series MACX Analog
Channels 2
Model Isolation Amplifier with SIL Functional Safety

electrical isolation 2 road isolation
Signal Transmission Behavior In = Out
maximum temperature coefficient ≤ 0.002 %/K (measured value/100 Ω load)
Typical transmission error 0.08 % (of terminal value)
electrical isolation
Test Voltage 2.5 kV AC (50 Hz, 60 s)
Overvoltage Category II
pollution level 2
Electrically isolated input/output/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
insulation security isolation
power supply
Supply Voltage Range loop power supply, no external power supply required

signals: current
Input Number 2
configurable/programmable No
Maximum voltage input signal < 30.5V
current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Input Voltage Limit 30.5V
voltage loss 2.9V (I = 20 mA)
step response (10-90%) 5 ms (500 Ω load)
additional error, depending on the load 0.022 % (measured value/100 Ω load)
response current ~ 50 &micro;A

signals: current
outputs 2
configurable/programmable No
Maximum voltage output signal 27.5V
current output signal 0 mA ... 20 mA
4 mA ... 20 mA
load/output load current output ≤ 1375 Ω (I = 20 mA)
residual wave < 10 mVrms(500 Ω load)

Connection Mode in-line connection
stripping length 10mm
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
flexible wire cross section (2 wires with the same cross section) 0.25 mm² ... 0.34 mm² (TWIN cold press head without plastic sleeve)
0.5 mm² ... 1.5 mm² (TWIN sleeve with plastic insulating sleeve)
2865340

Phoenix MACX MCR-SL-2I-2I-ILP-SP-Passive Isolator 2905281

Product Center