Phoenix MACX MCR-SL-CAC- 5-I-UP-Current Transmitter 2810625, Current Measurement Transmitter, Applicable Current 1A and 5A AC, Output Signal 0...20mA or 4...20mA, Configurable by DIP Switch, LED Display Working Status
Product Type
Current transmitter
insulation characteristics
Overvoltage Category
III
pollution level
2
Electrical characteristics
rated conditions
< 0.9W (24V DC)
< 3.4W (230V AC)
protection circuit
surge protection; 35V suppressor diode
step response (10-90%)
≤ 300 ms
200 ms
maximum temperature coefficient
< 0.02 %/K
temperature coefficient, typical
< 0.015 %/K
Maximum transmission error
≤ 0.5 % (in rated state, within rated range)
prevents polarity reversal
is
Rated insulation voltage
300V AC (ground)
electrically isolated input/output
Test Voltage
4 kV AC (50 Hz, 60 s)
galvanically isolated output/power supply
Test Voltage
2 kV AC (50 Hz, 60 s)
power supply
Supply Voltage Range
19.2V AC/DC ... 253V AC/DC
Maximum current consumption
< 33 mA (24V DC)
power consumption
< 0.8W (24V DC)
input data
measurement
configurable/programmable
via DIP switch
Input current range
0 A AC ... 1 A AC (configurable)
0 A AC ... 5 A AC (configurable)
voltage input signal
≤ 300V AC
input impedance
< 50 mΩ
Overload
2xIN ( sustained)
surge strength
20xIN ( 1s)
Rated frequency fN
50Hz
Frequency measurement range
45Hz ... 65Hz
Curve Type
Sine
Output Data
signals: current
configurable/programmable
via DIP switch
No-load voltage
15V
current output signal
0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Maximum current output signal
25 mA
load/output load current output
< 500 Ω (20 mA)
fluctuation
< 10 mVSS (500 Ω / 20 mA)
Status Display
Red LED (fault), Green LED (ready)