Phoenix MACX MCR-VAC-voltage measurement transmitter 2906239,MACX MCR voltage transmitter, used for AC voltage from 0V ... 20V AC to 0 ... 660V AC, output signal: 0V ... 10V/0(4) ... 20 mA

Product Type voltage transmitter

Span adjustment ± 20%
Zeroing ± 20%
protection circuit surge protection; 33V suppressor diode
step response (10-90%) < 180 ms
maximum temperature coefficient < 0.015 %/K
Maximum transmission error <1% (from end value of measuring range, 15Hz ... 65Hz)
< 1.3 % (from end of measuring range, 65Hz ... 405Hz)
electrical isolation
pollution level 2
galvanically isolated measuring circuit to power supply circuit and output IEC 61010-2-030
Standards/Regulations IEC 61010-2-030
Test Voltage 5.3 kV AC (50 Hz, 60 s)
Measurement Type II (1000 V)
III (600 V)
IV (300 V)
insulation reinforced insulation
electrically isolated power supply circuit to output circuit IEC 61010-1
Standards/Regulations IEC 61010-1
Test Voltage 2.2 kV AC (50 Hz, 60 s)
Overvoltage Category III (300 V)
IV (150 V)
insulation Foundation Isolation
Power
Rated supply voltage 24V DC (-20 % ... +25 %)
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 45 mA

measurement
configurable/programmable is
Input Voltage Range 0V AC ... 550V AC
Maximum input voltage +660V AC
Frequency Range 15Hz ... 405Hz
input voltage 5500 kΩ
impact waveform AC voltage
measurement
Input Voltage Range 0V AC ... 370V AC
input voltage 3700 kΩ
measurement
Input Voltage Range 0V AC ... 250V AC
input voltage 2500 kΩ
measurement
Input Voltage Range 0V AC ... 170V AC
input voltage 1700 kΩ
measurement
Input Voltage Range 0V AC ... 120V AC
input voltage 1200 kΩ
2906242