Phoenix AXL E IOL DO8 M12 6P-Digital Quantity Module 2702659,Axioline E, Digital Quantity Output Equipment, IO-Link Port Class B: 1, Wiring Mode: M12 Connector, A Code, Connection Technology: 5 Wire, Digital Output: 8,24V DC,500 mA, Connection Technology: 3 Wire, Plastic Case, Protection Level: IP65/IP67
| width |
60mm |
| height |
141mm |
| depth |
20mm |
| Notes on dimensional data |
height is 170mm, including fixing clip. 30mm depth with plug. |
| Application Description |
| Application Description |
for industrial applications only |
| Use Restrictions |
| EMC Description |
EMC: Class A products, see the manufacturer's declaration in the download area |
| Shell Material |
Pocan® |
| color |
coal ash RAL 7016 |
| IO-Link |
| ports |
1 |
| Connection Mode |
M12 connector, A- code |
| connection system |
Line 5 |
| Port Type |
Class B |
| Specification |
V1.1.2 |
| prevents polarity reversal |
is |
| transmission speed |
230.4 kbps (COM3) |
| cycle |
< 1 ms |
| Process Data Volume |
16 bits (output data) |
| digital quantity: |
| Output Name |
Digital Output |
| Connection Mode |
M12 Connector |
| connection system |
3 lines |
| outputs |
8 |
| protection circuit |
output; electronic |
| output voltage |
24V DC |
| Voltage limitation due to current interruption |
-28V ... -15V |
| output current |
Maximum 500 mA (per port) |
| max. 4 A (per device) |
| Rated output voltage |
24V DC (from voltage UA) |
| Minimum load |
10 kΩ |
| is disconnected |
Max. 1V |
| is disconnected |
Maximum 300 & micro;A |
| load rating, inductive |
12 VA max. (1.2 H,48 Ω, rated voltage) |
| rated load, indicator light |
maximum 12W (rated voltage) |
| Rated load, resistive |
12W max (48Ω, rated voltage) |
| Switching frequency |
maximum 1000 per second |
| max. 1 second (with inductive load) |
| Max. 16 per second (with nominal lamp load) |
| reverse voltage against short pulses |
limited protection up to 0.5 A for 1 s |
| overload behavior |
automatic restart |
| Inductor overload action |
output may be corrupted |
| signal delay |
maximum 100 & micro;s (at power-up) |
| maximum 100 & micro;s (with a minimum load current of 50 mA at shutdown) |