Phoenix AXL E PN IOL8 DI4 M12 6M-communication module 2701519,Axioline E,PROFINET,M12 connector, IO-Link port class a: 4, connection mode: M12 connector, connection technology: 3 wires, IO-Link port class B: 4, connection mode: M12 connector, connection technology: 3 wires, digital input at 2 of grade a port pin plug: 4, DC 24V, connection technology: 3-wire, metal housing, protection class: IP65/IP67

width 60mm
height 185mm
depth 38mm
hole spacing 198.5mm
Notes on dimensional data height is 194.5mm including the mounting plate. The height is 212mm with the retaining clip pulled out. The thickness is 38mm, including the mounting plate (30.5mm without mounting plate).

Application Description
Application Description for industrial applications only

Shell Material zinc die casting

PROFINET
interfaces 2
Connection Mode M12 Connector
Connection Method Considerations D coding
Bits 4
transmission speed 100 Mbps (Adaptive)
PROFINET
Device Type PROFINET-Device
System Specific Protocol PROFINET Transfer Protocol LLDP
PROFINET Transfer Protocol MRP Client
PROFINET Transfer Protocol DCP
PROFINET Transport Protocol DCE/RPC
Supported Protocols SNMP v1
HTTP
TFTP
FTP

digital quantity:
Enter Name Digital Input at Pin Plug 2 for Class A Port
Input Description IEC 61131-2 Type 1
Input Quantity 4
Connection Mode M12 connector, X01. .. X04 with dual channel
connection system 3 lines
input voltage range, "0" signal -0.3V DC ... 5V DC
input voltage range, "1" signal 15V DC ... 30V DC
Rated input voltage UIN 24V DC
Rated input current UIN Typical 3 mA
sensor current per channel Maximum 200 mA (off L /L-)
Total sensor current Maximum 1.6 A (off L /L-)
input frequency 0.5 kHz
input filter time < 1000 &micro;s
protection circuit overload protection, sensor power short circuit protection
2701517

Phoenix AXL E PN IOL8 DI4 M12 6M-Communication Module 2701519

Product Center