Phoenix AXL E PN IOL8 DI4 M12 6M-communication module 2701519,Axioline E,PROFINET,M12 connector, IO-Link port class a: 4, connection mode: M12 connector, connection technology: 3 wires, IO-Link port class B: 4, connection mode: M12 connector, connection technology: 3 wires, digital input at 2 of grade a port pin plug: 4, DC 24V, connection technology: 3-wire, metal housing, protection class: IP65/IP67
width
60mm
height
185mm
depth
38mm
hole spacing
198.5mm
Notes on dimensional data
height is 194.5mm including the mounting plate. The height is 212mm with the retaining clip pulled out. The thickness is 38mm, including the mounting plate (30.5mm without mounting plate).
Application Description
Application Description
for industrial applications only
Shell Material
zinc die casting
PROFINET
interfaces
2
Connection Mode
M12 Connector
Connection Method Considerations
D coding
Bits
4
transmission speed
100 Mbps (Adaptive)
PROFINET
Device Type
PROFINET-Device
System Specific Protocol
PROFINET Transfer Protocol LLDP
PROFINET Transfer Protocol MRP Client
PROFINET Transfer Protocol DCP
PROFINET Transport Protocol DCE/RPC
Supported Protocols
SNMP v1
HTTP
TFTP
FTP
digital quantity:
Enter Name
Digital Input at Pin Plug 2 for Class A Port
Input Description
IEC 61131-2 Type 1
Input Quantity
4
Connection Mode
M12 connector, X01. .. X04 with dual channel
connection system
3 lines
input voltage range, "0" signal
-0.3V DC ... 5V DC
input voltage range, "1" signal
15V DC ... 30V DC
Rated input voltage UIN
24V DC
Rated input current UIN
Typical 3 mA
sensor current per channel
Maximum 200 mA (off L /L-)
Total sensor current
Maximum 1.6 A (off L /L-)
input frequency
0.5 kHz
input filter time
< 1000 µs
protection circuit
overload protection, sensor power short circuit protection