Phoenix AXL F UTH8 1F-temperature module 2688417,Axioline F, temperature recording module, analog input: 8 (8 inputs for thermocouple or linear voltage, with 1 input,-5V to 5V), connection technology: 2 cores (shielded, twisted pair), local bus transmission rate: 100 Mbps, protection level: IP20, including bus base module and Axioline F connector
width
53.6mm
height
126.1mm
depth
54mm
Notes on dimensional data
using TH 35-7.5 rails (as EN60715).
Application Description
Application Description
for industrial applications only
Axioline F Local Bus
interfaces
2
Connection Mode
Bus Base Module
transmission speed
100 Mbps
Module
Input Address Area
18 Byte
Output Address Area
18 Byte
the required parameter data
27 Byte (20 bytes to configure GSD AXL UTH 8 (packing))
7 Byte
simulation
Enter Name
Analog Input
Input Description
Input for thermocouple or linear voltage
Input Quantity
8 1 (8 inputs for thermocouple or linear voltage, with 1 input,-5V to 5V)
Connection Mode
in-line connection
connection system
2-core (shielded, twisted pair)
A/D converter resolution
24.
Available Sensor Types (RTDs)
Pt 100(4 external cold junction compensation, can also be used as sensor input)
Available Sensor Types (TC)
U,T,L,J,E,K,N,S,R, B ,C,W,HK
measuring principle
Sigma/Delta Processing
Measurement Value Expression
16 bits (15 bits + sign bit)
input filter time
40 ms
60 ms
100 ms
120 ms (settable)
protection circuit
Short circuit protection for input, overload protection
input
Product Type
I/O components
product series
Axioline F
type
Modular structure
Installation position
anywhere (no temperature falloff; use object 0080hexParaTable! Set installation location parameters)