Phoenix AXL SE SSDI8/3-Safety module 1190012,Axioline Smart Elements, digital input module, functional safety, SafetyBridge technology, safe digital input: 4 (dual channel distribution),8 (single channel distribution),24V DC, connection Technology: 3 wires, protection level: IP20
| width |
14.9mm |
| height |
62.2mm |
| depth |
62mm |
| Application Description |
| Application Description |
for industrial applications only |
| Smart Element Interface |
| interfaces |
1 |
| Connection Mode |
Card Edge Connector |
| transmission speed |
See Systems Using Smart Element. |
| Module |
| Input Address Area |
6 Byte |
| Output Address Area |
5 Byte |
| digital quantity: |
| Enter Name |
Secure Digital Input |
| Input Description |
EN 61131-2, Class 3 |
| Input Quantity |
4 (dual channel distribution) |
| 8 (single channel distribution) |
| Cable Length |
maximum 200 m (200 m from clock output to safety input (all depends on forward and return path)) |
| Connection Mode |
in-line connection |
| connection system |
3 lines |
| input voltage range, "0" signal |
-3V DC ... 5V DC |
| input voltage range, "1" signal |
11V DC ... 30V DC |
| Rated input voltage UIN |
24V DC |
| Rated input current UIN |
Typical 2.7 mA |
| input filter time |
1.5 ms |
| 3 ms (default (value)) |
| 5 ms |
| 15 ms |
| protection circuit |
input polarity protection against reverse connection; diode |
| Product Type |
I/O components |
| Product Series |
Axioline Smart Elements |
| Application |
Functional Safety |
| SafetyBridge Technology |
| type |
Module |
| Installation position |
arbitrary |
| Mode of operation |
SafetyBridge |
| insulation characteristics |
| Overvoltage Category |
II (IEC 60664-1) |
| pollution level |
2 (EN 60664-1) |