Phoenix TRIO3-PS/1AC/24DC/10-power 1159038, primary switching power supply, TRIO POWER, in-line connection, DIN rail installation, input: 1 phase, output: 24V DC / 10 A, adjustable range 24V DC ... 28V DC

AC operation
Power System Configuration star network (TN,TT,IT (PE))
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
115V AC ... 240V AC ±10 % (UL)
Attenuation < 100V AC (1 %/V)
2.5 %/K,> 60°C
maximum dielectric strength 300V AC 15 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC
Impulse current < 17 A (25 °C)
impulse current integral (I2t) < 0.5 A2s
frequency range (fN) 50Hz ... 60Hz ± 10%
grid buffer time Typical 27 ms (120V AC)
Typical 28 ms (230V AC)
power consumption 2.6 A (100V AC)
2.2 A (120V AC)
1.2 A (230V AC)
1.1 A (240V AC)
protection circuit transient protection; varistor
power factor (cos phi) 0.95 (230V AC)
Device Power Fuse 6.3 A built-in (device protection)
recommend use 6 A ... 16 A (characteristics B, C, D, K or similar)
PE discharge current < 3.5 mA
DC operation
Input Voltage Range 100V DC ... 240V DC ±10%
160V DC ... 240V DC ±10 % (UL)
Attenuation < 140V DC (1 %/V)
power consumption 2.7 A (100V DC)
1.1 A (240V DC)

efficiency Typical 94.5 % (120V AC)
Typical 95.5 % (230V AC)
Rated output voltage 24V DC
output voltage (USet) setting range 24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 10 A
Dynamic Boost (IDyn.Boost) max. 15 A (5 s)
Short-circuit protection is
Anti-aircraft turn is
Attenuation 60°C ... 70°C
amplitude factor Typical 1.75 (120V AC)
Typical 1.7 (230V AC)
output power (PN) 240W
output power (Pdynamic margin) maximum 360W (5 s)
and connect Yes, for efficiency and redundancy
Concatenation Yes, for higher output voltages (in compliance with SELV limits)
feedback voltage resistance ≤ 35V DC
output ≤ 35V DC
1159037

Phoenix TRIO3-PS/1AC/24DC/10-Power 1159038

Product Center

PRODUCT CENTER