Phoenix TRIO3-PS/1AC/24DC/5-power supply 1159037, primary switching power supply, TRIO POWER, in-line connection, DIN rail installation, input: 1 phase, output: 24V DC/5 A, adjustable range 24V DC ... 28V DC
AC operation
Power System Configuration
star network (TN,TT,IT (PE))
Rated input voltage range
100V AC ... 240V AC
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
115V AC ... 240V AC ±10 % (UL)
Attenuation
< 100V AC (1 %/V)
2.5 %/K,> 60°C
maximum dielectric strength
300V AC 15 s
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC
Impulse current
< 33 A (25 °C)
impulse current integral (I2t)
< 0.55 A2s
frequency range (fN)
50Hz ... 60Hz ± 10%
grid buffer time
Typical 28 ms (120V AC)
Typical 28 ms (230V AC)
power consumption
1.3 A (100V AC)
1.1 A (120V AC)
0.6 A (230V AC)
0.59 A (240V AC)
protection circuit
transient protection; varistor
power factor (cos phi)
0.93 (230V AC)
Device Power Fuse
6.3 A built-in (device protection)
recommend use
6 A ... 16 A (characteristics B, C, D, K or similar)
PE discharge current
< 3.5 mA
DC operation
Input Voltage Range
100V DC ... 240V DC ±10%
160V DC ... 240V DC ±10 % (UL)
Attenuation
< 140V DC (1 %/V)
power consumption
1.29 A (100V DC)
0.53 A (240V DC)
efficiency
Typical 93% (120V AC)
94% typical (230V AC)
Rated output voltage
24V DC
output voltage (USet) setting range
24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN)
5 A
Dynamic Boost (IDyn.Boost)
Maximum 7.5 A (5 s)
Short-circuit protection
is
Anti-aircraft turn
is
Attenuation
60°C ... 70°C
amplitude factor
Typical 1.72 (120V AC)
Typical 1.89 (230V AC)
output power (PN)
120W
output power (Pdynamic margin)
Max. 180W (5 s)
and connect
Yes, for efficiency and redundancy
Concatenation
Yes, for higher output voltages (in compliance with SELV limits)