Phoenix PLC-RSC-230AC/21HC/SO46/HI-relay module 1079402, the PLC-INTERFACE includes PLC-BSC.../21HC/SO46/HI base terminals, using screw connection and in-line micro relay, suitable for high continuous current, 1 changeover Contact, rated input voltage 230V AC, with defined activation and deactivation thresholds
Product Type
Relay Module
Product Series
PLC-INTERFACE
Application
anti-interference filter
Mode of operation
100% operating factor
mechanical life
3x 107Switch Times
insulation characteristics: electrical clearance and creepage distance between power supply circuits
insulation
Foundation Isolation
Safe isolation, reinforced insulation and 6 kV between input circuit and output contact current paths
Overvoltage Category
III
pollution level
2
Data Management Status
Last data maintenance date
21.03.2025
rated conditions
1.04W
test voltage (coil/contact)
4 kV AC (50Hz,1 min, coil/contact)
Electrical clearance and creepage distance between power supply circuits
Rated overvoltage
4 kV
coil side
Rated input voltage UN
230V AC
Input Voltage Range
190V AC ... 264V AC (20 °C)
rated voltage ("hot" plug electromagnetic relay)
110V DC
closure threshold
190V AC
Disconnect Threshold
170V AC
drives and functions
monostable
drive (polarity)
polarization
UN
14 mA (50 Hz)
UNinput power consumption
3 VA
Typical Response Time
10 ms
Typical release time
8 ms
protection circuit
Bridge Rectifier
input circuit
RC element with threshold switch
Operating voltage display
yellow LED
switching
Contact Type
1 changeover contact
Switch Contact Type
Single contact
Contact Material
AgNi
maximum switching voltage
250V AC/DC (When the voltage between the same terminals of two adjacent modules is greater than 250V(L1, L2, L3), a spacer PLC-ATP must be used. FBST 8-PLC... or... FBST 500... for equipotential bridging)
Minimum Switching Voltage
12V (10 mA)
limit continuous current
10 A
6 A (This value only applies to terminal 12. If terminal 12 is shorted, the rating of the relay is used.)