Phoenix PSR-M-B2-XC-SDI8-SDO4-DO4-PI-safety module 1337849, configurable safety module (basic module), with 8 safety inputs, 4 safety outputs, 4 reset inputs or 4 signal outputs, 4 clock outputs, can be extended by TBUS, Up to SIL 3, Cat. 4/PL e, safety level, in-line terminal, no TBUS connector included

Product Type safety equipment
Application Emergency stop button
grating
safety door
Safety Shutdown
control Single and Dual Channel
response time See User Manual
restart time min. 5 s (start-up time)
max. 10 s (start-up time)

rated conditions 7.48W (with maximum allowable load)
Rated operating mode 100% Eligible
Interface DIN rail TBUS is used to connect the main station module, which is not included in the standard scope of supply
Electrical clearance and creepage distance between power supply circuits
rated overvoltage/insulation See chapter "Insulation Coordination"
Power
Name A1/A2
Rated control circuit supply voltage US 19.2V DC ... 28.8V DC
Rated control circuit supply voltage US 24V DC-20%/+ 20% (external fuse, typical 4 A)
Rated control supply current IS Typical 55 mA (output inactive)
US Typical 1.32W (output inactive)
Impulse current 9.16 A (Us, & Delta;t = 0.5 ms)
delay time typical 5 ms (Usvoltage dips)
protection circuit series protection to prevent polarity reversal

digital quantities: IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8
Input Description safety-related digital inputs
NPN
Input Quantity 8
input voltage range, "0" signal 0V DC ... 5V DC (for safety shutdown)
input voltage range, "1" signal 11V DC ... 28.8V DC
Input current range "0" signal < 0.2 mA
Impulse current maximum 524 mA (Us, & Delta;t = 6 & micro;s)
delay time 3 ms minimum (settable)
max. 250 ms (settable)
test pulse rate ≥ 2x set filter time, minimum test pulse rate = 10 ms
max. 3 ms (low test pulse filter time for test pulse rate ≥ 10x configuration)
max. 250 ms (high test pulse filter time for test pulse rate ≥ 10x configuration)
Cable Length 100 m max (per input)
Allowable Total Conductor Resistance max. 1.2 kΩ (US)
power consumption Typical 3.7 mA (Typical US)
maximum 4.6 mA (when the control voltage is 28.8V DC)
digital quantity: reset input (FBK)
Input Description configurable (as signal output or reset input)
NPN, Digital
Input Quantity 4
input voltage range, "0" signal 0V DC ... 5V DC (for safety shutdown)
input voltage range, "1" signal 11V DC ... 28.8V DC
Input current range "0" signal < 0.2 mA
Impulse current maximum 906.53 mA (& Delta;t = 10 & micro;s, at Us)
delay time 250 ms (constant)
1104975