Phoenix PSR-MC30-2NO-1DO-24DC-SC-safety relay 2700498, safety relay for emergency stop and safety door, meeting SILCL 3, category 4,PL e, single channel or dual channel operation, automatic or manual, monitoring start, cross circuit detection, 2 Enable current path, US = 24V DC, plug-in screw connector

Product Type safety relay
product series PSRmini
Application Emergency stop button
safety door
electromagnetic switch
control dual channel
mechanical life about 107Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical Response Time < 175 ms (auto start)
< 175 ms (manual, monitoring start)
Typical startup time (Us) < 250 ms (when controlled via A1)
Typical release time < 20 ms (via A1 as required)
< 20 ms (via sensor loop as required)
restart time < 1 s (start-up time, after power supply voltage is applied)
Recovery Time < 500 ms (meets the requirements of safety functions)
Start Pulse Length 500 ms (manual reset)

rated conditions 5.5W (US= 26.4 V, IL² = 72 A²,PTotal max=1.9W +3.6 W)
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation See chapter "Insulation Coordination"
Power
Name A1/A2
Rated control circuit supply voltage US 20.4V DC ... 26.4V DC
Rated control circuit supply voltage US 24V DC -15 % / +10%
Rated control supply current IS typical value 65 mA (US)
US Typical 1.56W
Impulse current typical 4 A (& Delta;t = 200 & micro;s Us)
filter time 1 ms (Usvoltage dips)
protection circuit series protection to prevent polarity reversal; suppression diode

digital quantity: sensor circuit (S12,S22)
Input Description safety-related sensor inputs
NPN (S12),NPN/PNP (S22)
Input Quantity 2
input voltage range, "0" signal < 5V (S12)
S22 interprets the low resistance output of the PLC as a continuous high signal.
input voltage range, "1" signal 20.4V ... 26.4V
Input current range "0" signal < 2 mA (S12)
0 mA ... 2 mA (S22)
Impulse current < 20 mA (S12 input, the voltage is usually US)
< 5 mA (typically USS22/24 V)
> -15 mA (typically USS22/0 V)
filter time max. 1.5 ms (at S12, S22; test pulse width)
7.5 ms minimum (at S12, S22; test pulse rate)
parallel
Allowable Total Conductor Resistance 150 Ω
protection circuit Suppressor Diode
power consumption < 5 mA (S12 input, voltage is usually US)
< 5 mA (typically USS22/24 V)
> -5 mA (typically USS22/0 V)
2700499

Phoenix PSR-MC30-2NO-1DO-24DC-SC-Safety Relays 2700498

Product Center

PRODUCT CENTER