Phoenix PSR-MC82-5NO-1NC-1DO-24DC-SC-expansion module 2702382, with evaluation module, contact expansion module can reach SIL 3, Cat. 4 and PL e standard levels, 5 normally open safety contact outputs, US = 24V DC, plug-in screw terminal

Product Type safety relay
Product Series PSRmini
Application Expansion Module
control Single and Dual Channel
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical Response Time < 50 ms (can be monitored/manual and automatic reset)
Typical startup time (Us) < 50 ms (when controlled via A1/A2)
Typical release time < 25 ms (when controlled via A1/A2)
Recovery Time < 100 ms

rated conditions 15.2W (in US= 30 V, IL² = 64 A²)
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation
Power
Name A1/A2
Rated control circuit supply voltage US 19.2V DC ... 30V DC
Rated control circuit supply voltage US 24V DC -20 % / +25%
Rated control supply current IS 80 mA typical
US Typical 1.92W
Impulse current Typical 125 mA (& Delta;t = 7 ms Us)
filter time 4 ms (at A1, at the voltage dip Us)
max. 1 ms (test pulse width at A1/A2, blanking pulse/dark test)
5 ms (A1/A2, test pulse rate, blanking pulse/dark test)
test pulse width <1 ms: test pulse rate = 5 x test pulse width
max. 1 ms (test pulse width at A1/A2, switch pulse/light gap test)
10 ms (at A1/A2; test pulse rate; switching pulse/optical gap test)
For safety applications, the switching pulse is disabled.
protection circuit Surge protection; Suppressor diode
polarity protection; general purpose diode

relay: enable current path (23/24 ... 63/64)
Output Description safety-related normally open contacts
outputs 5 (non-delayed)
Contact Type 5 normally open safety contact outputs
Contact Material AgSnO2
Switching voltage Minimum 5V AC/DC
maximum 24V DC (starting current path 23/24)
max. 250V AC/DC (see load curve for all other enabled current paths)
On-Off Capacity 50 mW (5V / 10 mA) minimum
Impulse current 10 mA minimum
max. 20 A (≤ 100 ms)
limit continuous current 6 A (pay attention to capacity reduction)
the square of the total current value 64 A2(pay attention to capacity reduction)
Switching frequency max. 0.5Hz
mechanical life 10x 106Switch Times
output fuse 10 A gL/gG
6 A gL/gG (for low-demand applications)
Relays: Way Feedback Loops (11/12)
Output Description safety-related normally closed contacts
outputs 1 (non-delayed)