Phoenix PSR-M-EF1-SDI8-SDO4-DO4-SC-expansion module 1104890, safety expansion module, with 8 safety inputs, 4 safety outputs, 4 reset inputs or 4 signal outputs, 4 clock outputs, TBUS interface, safety level up to SIL 3, Cat. 4/PL e, pluggable screw terminal block, with TBUS connector included

Product Type safety equipment
Application Emergency stop button
grating
safety door
Safety Shutdown
control Single and Dual Channel
insulation characteristics
protection level III
insulation characteristics
Overvoltage Level II
pollution level 2
response time see user manual
restart time 5 s minimum (start-up time)
max. 10 s (start-up time)

rated conditions 7.48W (with maximum allowable load)
Rated operating mode 100% Eligible
Interface DIN rail TBUS for connecting the host module, within the scope of delivery
rated overvoltage/insulation 4 kV base isolation between 24V supply and I/O and enclosure
power supply
Name A1/A2
Rated control circuit supply voltage US 19.2V DC ... 28.8V DC
Rated control circuit supply voltage US 24V DC-20%/+ 20% (external fuse, typical 4 A)
Rated control supply current IS Typical 45 mA (output inactive)
Typical 68 mA (output enabled, no load)
US Typical 1.08W (output inactive)
Impulse current < 2.3 A (&Delta;t = 1 ms Us)
filter time typical 5 ms (at A1, at the voltage dip Us)
protection circuit series protection to prevent polarity reversal

digital quantities: IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8
Input Description safety-related digital inputs
IEC 61131-2 Type 2
Input Quantity 8
input voltage range, "0" signal 0V DC ... 5V DC
input voltage range, "1" signal 11V DC ... 28.8V DC
Input current range "0" signal < 1 mA
filter time 3 ms ± 2 ms minimum (settable)
max. 250 ms ± 2 ms (settable)
test pulse rate ≥ 2x set filter time, minimum test pulse rate = 10 ms
Cable Length 100 m max (per input)
Allowable total conductor resistance max. 1.2 kΩ (US)
power consumption typical value 10 mA (in U.Stypical)
maximum 12.5 mA (when the control voltage is 28.8V DC)
digital quantity: reset input (FBK)
Input Description configurable (as signal output or reset input)
IEC 61131-2 Type 2
1104975

Phoenix PSR-M-EF1-SDI8-SDO4-DO4-SC-Extension Module 1104890

Product Center