Phoenix PSR-M-GW-CCLINK-PI-data interface 1105129, used to connect the PSR-M base module to the gateway of the higher-level controller, supports CC-Link protocol, TBUS interface, pluggable in-line terminals, and includes TBUS connector
rated conditions
0.75W
Rated operating mode
100% Eligible
Interface
DIN rail TBUS for connecting the host module, within the scope of delivery
rated overvoltage/insulation
4 kV foundation isolation
power supply
Name
A1/A2
Rated control circuit supply voltage US
19.2V DC ... 28.8V DC
Rated control circuit supply voltage US
24V DC-20%/+ 20% (external fuse, typical 4 A)
Rated control supply current IS
Typical 30 mA (no network connection)
Typical 30 mA (1 network interface)
US
Typical 0.75W (1 network interface)
Impulse current
< 2.2 A (Δt = 1 ms Us)
filter time
typical 5 ms (at A1, at the voltage dip Us)
protection circuit
series protection to prevent polarity reversal
suppression diode
Connection Mode
in-line connection
stripping length
10mm
data: network interface
Communication Transport Protocol
CC-Link V 2
Connection Mode
plug-in connector
connection quantity
1
Bits
5
Considerations
electrical isolation
transmission speed
10 Mbps
5 Mbps
2.5 Mbps
625 kbps
156 kbps
Data: Service Interface
Connection Mode
High-speed USB 2.0
connection quantity
1
Status Display
1 x LED (green),1 x LED (green, red),1 x LED (red)