Phoenix PSR-MS20-1NO-1DO-24DC-SC-safety relay 2904950, safety relay for emergency stop and safety door, meets SIL 1, Cat. 1,PL c, according to different applications, can meet SIL 3, Cat. 4,PL e, single channel operation, automatic start, 1 start current path, Us = 24V DC, fixed screw connector

Product Type safety relay
Product Series PSRmini
Application Emergency stop button
safety door
electromagnetic switch
control single channel
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical Response Time < 175 ms
Typical startup time (Us) < 250 ms (when controlled via A1)
Typical release time < 20 ms (when controlled via A1 or S12)
restart time < 1 s (start-up time)
Recovery Time < 500 ms

rated conditions 3W (US= 26.4 V, IL² = 36 A²,PTotal max= 1.2W +1.8 W)
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation input circuit and normally open safety contact output
4 kV foundation safety isolation between all current paths and enclosure
Power
Name A1/A2
Rated control circuit supply voltage US 20.4V DC ... 26.4V DC
Rated control circuit supply voltage US 24V DC -15 % / +10%
Rated control supply current IS Typical 42 mA
US Typical 1W
Impulse current 4.5 A (&Delta;t < 120 &micro;s Us)
filter time 1 ms (at A1, at the voltage dip Us)
protection circuit Surge protection; Suppressor diode
series protection to prevent polarity reversal

digital quantity: sensor circuit (S12)
Input Description safety-related sensor inputs
Input Quantity 1
input voltage range, "0" signal 0V DC ... 5V DC (for safety shutdown; at S12)
input voltage range, "1" signal 20.4V DC ... 26.4V DC
Input current range "0" signal 0 mA ... 2 mA (for safety shutdown; at S12)
Impulse current < 20 mA (US)
filter time max. 1.5 ms (test pulse width of low test pulse)
test pulse rate = 5 x test pulse width
Allowable Total Conductor Resistance 150 Ω
protection circuit Suppressor Diode
power consumption < 5 mA (US)
digital quantity: start circuit (S35)
Input Description non-safety related
Input Quantity 1
input voltage range, "1" signal 20.4V DC ... 26.4V DC
Impulse current < 10 mA
Allowable Total Conductor Resistance 150 Ω
protection circuit Suppressor Diode
power consumption < 10 mA

relay: starting current path (13/14)
Output Description safety-related normally open contacts
outputs 1 (non-delayed)
Contact Type 1 starting current path
Contact Material AgSnO2
Switching voltage minimum 12V AC/DC
2904951

Phoenix PSR-MS20-1NO-1DO-24DC-SC-Safety Relays 2904950