Phoenix PSR-PC20-1NO-1NC-24DC-SP-coupling relay 2700578, suitable for SIL 3 high-demand and low-demand applications, can connect digital output signals to peripherals, 1 enable current path, 1 confirm current path, 1 digital signal Output, safe state shutdown application, test pulse filter, TBUS connection, pluggable in-line terminal block
Product Type
coupling relay
Product Series
PSRmini
Application
Safety Shutdown
high requirements
low requirements
Ex
control
single channel
Relay Model
Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level
III
pollution level
2
Typical startup time (Us)
< 100 ms (when controlled by A1, there is us)
Typical release time
< 35 ms (when controlled via A1)
Recovery Time
500 ms
rated conditions
3.43W (IL² = 36 A²)
Rated operating mode
100% Eligible
Rated insulation voltage
250V AC
rated overvoltage/insulation
safety isolation, 6 kV reinforced insulation of control circuits, start circuit, confirmation current path, signal output to enable current path; 4 kV/basic insulation between all current paths and enclosure
Power
Name
A1/A2
Rated control circuit supply voltage US
20.4V DC ... 26.4V DC
Rated control circuit supply voltage US
24V DC -15 % / +10%
Rated control supply current IS
Typical 50 mA
US
Typical 1.2W
Impulse current
Typical 400 mA (& Delta;t < 10 & micro;s Us)
filter time
max. 2 ms (in A1-A2; test pulse width)
≥ 100 ms (at A1-A2; test pulse rate)
protection circuit
Series protection against polarity reversal; 33V suppressor diode
Power
Name
31/A2, TBUS
Diagnostic supply voltage UD
24V DC -15 % / +10%
UDinput current
6 mA (on 31-A2, for UD; depending on load +100 mA(M1 and 32 places))
UD
Typical 2.5 A (& Delta;t < 20 & micro;s UD)
protection circuit
Series protection against polarity reversal; 33V suppressor diode
relay: starting current path (13/14 (13F/14))
Output Description
Every 2 normally open contacts in series, no delay, floating ground
outputs
1 (safety related)
Contact Type
1 starting current path
Contact Material
AgSnO2
Switching voltage
minimum 12V AC/DC
Max. 250V AC/DC
on-off capacity
60 mW minimum
Impulse current
3 mA minimum
max. 6 A (normally open contact 13/14)
4 A (normally open contact 13F/14)
limit continuous current
6 A (13/14 for high demand)
4 A (13F/14 high/low requirement, 13/14 low requirement)