Phoenix MCR-SL-S-200-U-current transmitter 2813460,MCR current measurement transmitter, used to measure sinusoidal and non-sinusoidal AC currents, input current 0...200 A, output voltage 0...(5)10V
| Product Type | Current transmitter |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| rated conditions | 1W |
| test voltage, input/output | 4.13 kV AC (50 Hz, 60 s) |
| step response (10-90%) | < 340 ms |
| maximum temperature coefficient | < 0.035 %/K |
| Maximum transmission error | <1% (of terminal value) |
| Rated insulation voltage | 300V AC (ground) |
| power supply | |
| Rated supply voltage | 24V DC |
| Supply Voltage Range | 20V DC ... 30V DC |
| Maximum current consumption | < 30 mA |
| signal | |
| configurable/programmable | is |
| current input signal | 0 A ... 200 A |
| measurement | |
| Input current range | 0 A AC ... 100 A AC |
| 0 A AC ... 150 A AC | |
| 0 A AC ... 200 A AC | |
| minimum input current | 0 A AC ... 100 A AC |
| maximum input current | 0 A AC ... 200 A AC |
| Overload | depends on bottom wire |
| surge strength | depends on the wire connected by the perforation. |
| Frequency measurement range | 30Hz ... 6000Hz |
| Curve Type | sinusoidal and non-sinusoidal |
| Operating Threshold | 1% (of terminal value) |
| signals: voltage | |
| voltage output signal | 0V ... 5V |
| 0V ... 10V | |
| Maximum voltage output signal | (0V ... 10 V) 14 V,(0 V ... 5 V) 7V |
| load/output load voltage output | ≥ 10 kΩ |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 2.5 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.) |
| Connection Mode | perforated connection |
| Product Size | |
| width | 55mm |
| height | 85mm |
| depth | 70.5mm |
| Round wire | |
| diameter | ≤ 18.5mm |
| color | green (RAL 6021) |
| Shell Material | Non-reinforced polyamide PA |