Phoenix TTC-6-2XTVSD-24DC-PT-surge protector 2906808 for fine surge protection of two signal lines with a common reference potential. Can be used in safety-related circuits up to SIL 3.
| Product Type | measurement and control technology |
| Product Series | TERMITRAB complete |
| IEC Category | C1 |
| C3 | |
| type | rail mounting module, monolithic |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 24V DC |
| Connection Mode | in-line connection |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 6.2mm 0.1mm |
| height | 105.8mm |
| depth | 69.5mm (7.5mm with DIN rail) |
| color | gray (RAL 7042) |
| light gray (RAL 7035) | |
| flame retardant rating, according to UL 94 | V-0 |
| insulation material | PBT |
| Shell Material | PBT |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Earth Ground |
| Maximum continuous voltage Uc | 30V DC |
| 21V AC | |
| Rated current | 6 A (55 °C) |
| Residual Flow IPE | ≤ 10 µA |
| Rated discharge current In(8/20)& micro;s (core-ground) | 0.5 kA |
| Total discharge current ITotal(8/20) µs | 1 kA |
| voltage protection level Up(line-ground) | ≤ 60V (C1 - 1 kV / 500 A) |
| ≤ 45V (C3 - 25 A) | |
| ≤ 50V (C3 - 100 A) | |
| response time tA (core-ground) | ≤ 1 ns |
| input attenuation AE, asymmetric. | Typical 0.3 dB (≤ 300 kHz / 150 Ω) |
| cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system | Typical 960 kHz |
| capacitance (core-ground) | Typical 2.2 nF |
| the resistance of each path | ≤ 100 mΩ |
| Surge protection fault alarm | None |
| 6.3 A (FF) | |
| Impact resistance (line-ground) | C1 - 1 kV / 500 A |
| C3 - 100 A |
| environmental conditions | |
| protection level | IP20 |