Phoenix TTC-6-2XTVSD-24DC-PT-surge protector 2906808 for fine surge protection of two signal lines with a common reference potential. Can be used in safety-related circuits up to SIL 3.

Product Type measurement and control technology
Product Series TERMITRAB complete
IEC Category C1
C3
type rail mounting module, monolithic
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 24V DC

Connection Mode in-line connection
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 6.2mm 0.1mm
height 105.8mm
depth 69.5mm (7.5mm with DIN rail)

color gray (RAL 7042)
light gray (RAL 7035)
flame retardant rating, according to UL 94 V-0
insulation material PBT
Shell Material PBT

Mechanical parameters
Open Side Panel No

movement direction Line-Earth Ground
Maximum continuous voltage Uc 30V DC
21V AC
Rated current 6 A (55 °C)
Residual Flow IPE ≤ 10 µA
Rated discharge current In(8/20)& micro;s (core-ground) 0.5 kA
Total discharge current ITotal(8/20) µs 1 kA
voltage protection level Up(line-ground) ≤ 60V (C1 - 1 kV / 500 A)
≤ 45V (C3 - 25 A)
≤ 50V (C3 - 100 A)
response time tA (core-ground) ≤ 1 ns
input attenuation AE, asymmetric. Typical 0.3 dB (≤ 300 kHz / 150 Ω)
cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system Typical 960 kHz
capacitance (core-ground) Typical 2.2 nF
the resistance of each path ≤ 100 mΩ
Surge protection fault alarm None
6.3 A (FF)
Impact resistance (line-ground) C1 - 1 kV / 500 A
C3 - 100 A

environmental conditions
protection level IP20
2906798

Phoenix TTC-6-2XTVSD-24DC-PT-Surge Protector 2906808

Product Center

PRODUCT CENTER