Phoenix TTC-6-MOV-C-120AC-UT-I-surge protector 2906840, medium surge protection, built-in status indicator, for a signal line with ground reference potential. Can be used in safety-related circuits up to SIL 3.
| Product Type | measurement and control technology |
| product series | TERMITRAB complete |
| IEC Category | C1 |
| C2 | |
| C3 | |
| type | rail mounting module, monolithic |
| Surge protection fault alarm | with visual status indication window |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 120V AC |
| Connection Mode | screw connection |
| thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 6.2mm |
| height | 92mm |
| depth | 69.5mm (7.5mm with DIN rail) |
| color | gray (RAL 7042) |
| flame retardant rating, according to UL 94 | V-0 |
| insulation material | PBT |
| Shell Material | PBT |
| Mechanical parameters | |
| Open Side Panel | is |
| movement direction | Line-Earth Ground |
| Maximum continuous voltage Uc | 150V DC |
| 150V AC | |
| Rated current | 10 A (60 °C) |
| UC, the effective working current IC | ≤ 100 µA |
| Residual Flow IPE | ≤ 100 µA |
| Rated discharge current In(8/20)& micro;s (core-ground) | 2.5 kA |
| voltage protection level Up(line-ground) | ≤ 200V (C1 - 800 A) |
| ≤ 500V (C2 - 5 kV) | |
| ≤ 380V (C3 - 25 A) | |
| ≤ 380V (C3 - 35 A) | |
| response time tA (core-ground) | ≤ 25 ns |
| input attenuation AE, asymmetric. | Typical 0.3 dB (≤ 300 kHz / 150 Ω) |
| cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system | Typical 1 MHz |
| capacitance (core-ground) | 5 nF |
| the resistance of each path | ≤ 100 mΩ |
| Surge protection fault alarm | with visual status indication window |
| Impact resistance (line-ground) | C1 - 800 A |
| C2 - 2.5 kA | |
| C3 - 35 A |