Phoenix TTC-6P-2X1-M-EX-24DC-UT-I-surge protector 2906825, surge protection, including protection plug and base element, built-in status indicator and breaking switch, used for 2-wire Ex I signal circuit with common reference potential, such as digital quantity IN/OUT. Can be used in safety-related circuits up to SIL 3.
Product Type
measurement and control technology
product series
TERMITRAB complete
IEC Category
C1
C2
C3
D1
type
DIN rail module, split, detachable
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated voltage UN
24V DC
Connection Mode
screw connection
thread
M3
Tightening torque
0.5 Nm ... 0.6 Nm
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG
24 ... 12
Maximum internal capacitance CI
Negligible
Maximum internal inductance LI
Negligible
Maximum input current II
400 mA (T4 / -40°C ... 50°C)
250 mA (T4 / -40°C ... 70°C)
350 mA (T6 / -40°C ... 35°C)
100 mA (T6 / -40°C ... 70°C)
Maximum input voltage UI
30V DC
ambient temperature (operation)
-40°C ... 70°C (with current decay)
Dimensional drawing
width
6.2mm 0.1mm
height
105.8mm
depth
100 mm (7.5mm with DIN rail)
color
blue (RAL 5015)
flame retardant rating, according to UL 94
V-0
insulation material
PBT
Shell Material
PBT
Mechanical parameters
Open Side Panel
No
movement direction
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage Uc
30V DC
Rated current
600 mA (40°C)
UC, the effective working current IC
≤ 5 µA
Residual Flow IPE
≤ 10 µA
Rated discharge current In(8/20)& micro;s (core-ground)
5 kA
pulse discharge current Iimp(350) & micro;s (core-ground)