Phoenix TTC-6P-3-HF-F-M-12DC-UT-I-surge protector 2906786, surge protection, including protection plug and base element, built-in status indicator and knife switch, for three signal cables with common reference potential. Suitable for high frequency applications and communication interfaces without supply voltage. Indirect grounding through the gas discharge tube, suitable for EX e certification in zone 2. Can be used in safety-related circuits up to SIL 3.
| Product Type | Information Technology |
| Product Series | TERMITRAB complete |
| IEC Category | C1 |
| C2 | |
| C3 | |
| D1 | |
| type | DIN rail module, split, detachable |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 12V DC |
| Connection Mode | screw connection |
| thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Maximum input current | 600 mA (T4 / ≤ 30°C) |
| 500 mA (T4 / > 30°C ... ≤ 50°C) | |
| 400 mA (T4 / > 50°C ... ≤ 70°C) | |
| Maximum input voltage | 15V DC |
| elevation | ≤ 2000 m (amsl) |
| ambient temperature (operation) | -40°C ... 70°C (T4) |
| Dimensional drawing | |
| width | 6.2mm 0.1mm |
| height | 105.8mm |
| depth | 100 mm (7.5mm with DIN rail) |
| color (basic element) | gray (RAL 7042) |
| color (pin connector) | light gray (RAL 7035) |
| flame retardant rating, according to UL 94 | V-0 |
| insulation material | PBT |
| Shell Material | PBT |
| Mechanical parameters | |
| Open Side Panel | No |