Phoenix TTC-6P-T3-24DC-UT-I-3 surge protection equipment 1027584, type 3 surge protection, including protective connectors and base elements, built-in status indicator for 24V DC power supply
| Overview | |
| Considerations | CBM: |
| 2905743 CBM E4 24DC/0.5-10A NO-R | |
| 2905744 CBM E8 24DC/0.5-10A NO-R | |
| CBMC: | |
| 2906032 CBMC E4 24DC/1-10A NO | |
| 2908716 CBMC E4 24DC/1-10A NO-C | |
| 2910411 CBMC E4 24DC/1-10A IOL | |
| PTCB: | |
| 2908262 PTCB E1 24DC/1-8A NO | |
| CB E1: | |
| 2800907 CB E1 24DC/10A NO P | |
| 2800914 CB E1 24DC/10A S-R P | |
| 2800928 CB E1 24DC/10A S-C P | |
| 2905805 CB E1 24DC/10A SI-R P | |
| 2905812 CB E1 24DC/10A SI-C P | |
| Product Type | Equipment Protection |
| product series | TERMITRAB complete |
| IEC power supply system | DC |
| type | DIN rail module, split, detachable |
| Bits | 2 |
| Surge protection fault alarm | with visual status indication window |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| IEC Category | III |
| T3 | |
| EN Type | T3 |
| Ports | One |
| Connection Mode | screw connection |
| thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 6.2mm 0.1mm |
| height | 105.8mm |
| depth | 100 mm (7.5mm with DIN rail) |
| color (basic element) | gray (RAL 7042) |
| color (pin connector) | light gray (RAL 7035) |
| flame retardant rating to UL 94 | V-0 |
| material | 600 |
| insulation material | PBT |
| Shell Material | PBT |
| power supply | |
| movement direction | 1L-N & N-PE |
| Rated voltage UN | 24V DC |
| Maximum continuous voltage Uc | 30V DC |
| Rated load current IL | 6 A (30 °C) |
| Residual Flow IPE | ≤ 5 µA |
| Nominal discharge current In(8/20)µs | 1 kA |
| Combined surge UOC | 2 kV (2 Ω) |
| 2 kV (2 Ω) | |
| voltage protection level Up(DC ) - (DC-) | ≤ 0.09 kV (Uoc= 2 kV) |
| ≤ 0.2 kV (Uoc= 6 kV) | |
| voltage protection level Up(DC /DC-) - PE | ≤ 0.7 kV |
| Rated short-circuit current ISCCR | 60 A DC (no additional backup protection fuse required) |
| 220 A DC | |
| maximum spare fuse with branch wiring | 6 A (gG) |
| 10 A (see instructions: CBM, CBMC, PTCB, CB E1) | |