Phoenix EEM-MB370-24DC-measuring device 1127061, multifunctional energy measuring device, without display, using 24V DC power supply and integrated Modbus/TCP interface, used to measure electrical parameters in low-voltage devices up to 690V

Product Type Electric energy monitoring equipment
product series EMpro

rated conditions 10 VA
Main Power Type 3-phase (3 or 4-wire system), dual-phase (2-wire system) and single-phase (single-wire system)
electrical isolation
Test Voltage 4 kV AC (50 Hz, 60 s)
pollution level 2
insulation reinforced insulation
electrical isolation housing relative to all potentials IEC 61010-1
Standards/Regulations IEC 61010-1
Overvoltage Category III (300V AC)
II (600V AC)
insulation reinforced insulation
galvanically isolated supply voltage
insulation Functional insulation
galvanically isolated voltage measurement input relative to all other potentials IEC 61010-2-030
Standards/Regulations IEC 61010-2-030
Measurement Type III (300V AC)
II (600V AC)
insulation reinforced insulation
galvanically isolated current measurement input relative to all other potentials
insulation Functional insulation
galvanically isolated digital I/O
insulation Functional insulation
electrical isolation communication interface
insulation Functional insulation
power supply
supply voltage 24V DC ±25%
Supply Voltage Range 18V DC ... 30V DC
power consumption < 4W

Overview
measuring principle True effective value measurement
measured value AC sinusoidal (50Hz/60Hz)
harmonic current acquisition up to 63rd harmonic
Input Description digital input conforming to IEC/EN 61131-2 (type 3)
number. 1
voltage input signal 24V DC
0V DC ... 30V DC
current input signal 2 mA ... 15 mA
protection 250 mA (fast fuse)
protection circuit Prevent wrong DC connection (max. 30V)
measurement: voltage
Enter Name voltage measurement inputs V1,V2,V3
Input Voltage Range Direct 35V AC ... 690V AC (phase/phase)
20V AC ... 400V AC (phase/neutral conductor)
input voltage range via external current transformer 60V AC ... 2000000V AC (Primary)
60V AC ... 400V AC (secondary)
surge power 760V AC (phase/phase)
accuracy 0.2 percent
power consumption < 2 VA
measurement: current
Enter Name current measurement I1, I2, I3
input current 1 A (secondary)
5 A (secondary)
Measurement range 1 A ... 20000 A (primary)
Overload 6 A (Ithe largest)
2907984

Phoenix EEM-MB370-24DC-Measuring Equipment 1127061

Product Center

PRODUCT CENTER