Phoenix EEM-PM157-SLP-measuring equipment 1269236, DC energy measuring equipment, direct measurement capacity up to 1000V/650 A, equipped with RS-485 interface for software programming and connection to DC charge controller, can correct charging cable losses, operating temperature Up to +80°C, certified for billing purposes

Product Type Energy Measuring Equipment
product series EMpro
(charging process) > 225000 (start and stop charging record)
(Calibration Log Capacity) > 2500
insulation characteristics
Overvoltage Category III
pollution level 2

dielectric strength 3521V (IEC 61851-23, EN 62052-31)
power supply
Supply Voltage Range 19.2V DC ... 36V DC

measurement
Input Voltage Range 150V DC ... 1000V DC
Input current range 6.5 A ... 650 A (direct measurement)
power consumption < 5W
< 0.5W (UN)
< 0.12W (Ithe largest)
starting current Ist 0.52 A
Minimum current Imin 6.5 A
Limiting current Imax 650 A
Transient current Itr 13 A
Reference current Iref 130 A

Pulse LED 1000 imp/kWh (metering LED)

voltage
Connection Mode screw connection
Rigid conductor cross section 0.75 mm² ... 1.5 mm²
Flexible Wire Cross Section 0.75 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 20 ... 16
Tightening torque 0.5 Nm ... 0.6 Nm
current
Connection Mode screw connection
thread M8
M10
Tightening torque 17.5 Nm ... 20 Nm

Communications:
Communication Transport Protocol SLIP
communication standard RS-485
3
Connection Mode RJ12
transmission speed (Interface 1 and 2) 19200 bps (8N1 (configurable))
transmission speed (Interface 3) 115200 bps (8N1 (configurable))
Transmission speed range 9600 bps ... 115200 bps (settable)

Dimensional drawing
width 107.2mm
height 115.6mm
depth 66.75mm

environmental conditions
protection level IP20
Ambient temperature (operation) -40°C ... 80°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation ≤ 2000 m
maximum allowable relative humidity (operating) 97.5 % (no condensation)
1269236