Phoenix LIT 4X1-24-Surge protector 2804649, one-piece surge protector, 6.2mm thick, installed on DIN rail, used to protect 4 signal lines with common reference potential.
Product Type
measurement and control technology
Product Series
LINETRAB
IEC Category
C1
C2
C3
D1
type
rail mounting module, monolithic
Surge protection fault alarm
None
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated voltage UN
24V DC
Connection Mode
screw connection
thread
M3
Tightening torque
0.8 Nm
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 14
Dimensional drawing
width
6.2mm
height
93.1mm
depth
102.5mm (7.5mm with DIN rail)
color
Smoke gray (RAL 7016)
flame retardant rating to UL 94
V-0
insulation material
PBT
Shell Material
PBT
Mechanical parameters
Open Side Panel
No
movement direction
Line-Earth Ground
Maximum continuous voltage Uc
36V DC
25V AC
Rated current
350 mA (40°C)
UC, the effective working current IC
≤ 2 µA
Residual Flow IPE
≤ 8 µA
Rated discharge current In(8/20)& micro;s (core-ground)
5 kA
pulse discharge current Iimp(350) & micro;s (core-ground)
500 A
2 kA (total)
Total discharge current ITotal(8/20) µs
20 kA
Maximum discharge current Imax(8/20) & micro;s (core-ground)
10 kA
20 kA (total)
rated power pulse current lan (1000)& micro;s (core-ground)
50 A
200 A (total)
Output voltage limit 1 kV/& micro;s (core-ground) peak
≤ 60V
Residual voltage ln,(wire-ground)
≤ 50V
Ian(10/1000)& micro; Residual pressure at s (line-ground)
≤ 60V
voltage protection level Up(Line-Ground)
≤ 60V (C1 - 500V / 250 A)
≤ 95V (C2 - 10 kV / 5 kA)
≤ 55V (C3 - 10 A)
≤ 55V (C3 - 50 A)
≤ 250V (D1 - 500 A)
response time tA (core-ground)
≤ 1 ns
input attenuation AE, asymmetric.
Typical 0.3 dB (1 MHz/50 Ω)
Typical 0.2 dB (350 kHz/150 Ω)
cutoff frequency fg(3 dB), asymmetric. (PE) in a 50 Ω system
Typical 6 MHz
cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system