Phoenix ELR 1-SC-230AC/600AC-30-Solid state contactor 1032922, single-phase solid state contactor, input voltage: 230V AC, output current: 30 A, zero voltage switching

Product Type solid state contactor

phase number 1
rated conditions 28W
Main Power Type single phase

control
Enter Name Control Input
Rated operating voltage UC 230V AC
Trigger voltage range 24V AC ... 275V AC
24V DC ... 190V DC
Rated operating current IC approx. 17 mA
Switch Threshold ≤ 5V AC/DC ("0" signal)
≥ 20V AC/DC ("1" signal)
Operating voltage display Green LED
transmission frequency 6Hz

load output
Operating voltage range 42V AC ... 660V AC
AC-51 30 A
AC-53a 15 A (TA= 25°C)
5 A (TA= 40°C)
peak quiescent voltage 1200V
mains frequency 45Hz
65Hz
Load current range 250 mA ... 30 A (see attenuation curve)
leakage current < 3 mA (in disconnected state)
residual pressure < 1V
surge current 600 A (t = 10 ms)
Maximum load value 1800 A2s
protection circuit varistor
minimum phase angle cos phi 0.5

control loop
Connection Mode screw connection
stripping length 8mm
thread M3
Rigid conductor cross section 0.5 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.5 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 18 ... 12
Load Circuit
Connection Mode screw connection
stripping length 12mm
thread M4
Rigid conductor cross section 2.5 mm² ... 6 mm²
Flexible Wire Cross Section 1 mm² ... 4 mm²
Attachable Guide Cross Section AWG 14 ... 10
protective wire connection
Connection Mode ring cable pin
thread M5
Tightening torque 1.5 Nm

Operating voltage display Green LED

width 18mm
height 110mm
depth 103mm

color gray (RAL 7042)

environmental conditions
ambient temperature (operation) -30°C ... 70°C
ambient temperature (storage/transport) -40°C ... 80°C