Phoenix ELR H3-IES-SC-230AC/500AC-2-hybrid motor starter 2900568, hybrid motor starter, used to start AC motors with more than 3 phases, up to 550V AC,230V AC input, 2.4 A output current, emergency stop function, Adjustable overload breaking.

Product Type hybrid motor starter
Product Series CONTACTRON
Mode of operation 100% operating factor

phase number 3
Motor Starter Type direct starter
Switching frequency ≤ 2Hz (depending on load)
rated conditions 2.2W
Switching frequency ≤ 2Hz (depending on load)
maximum power loss 4.7W
minimum power loss 2.6W
type of coordination 1
power supply
Rated control circuit supply voltage US 230V AC
Control Supply Voltage Range 85V AC ... 253V AC
Rated control supply current IS 4 mA
mains frequency 50/60Hz
protection circuit surge protection
insulation characteristics
Rated insulation voltage 500V
Rated overvoltage 4 kV
Overvoltage Level III
pollution level 2
control input and control supply voltage and insulation characteristics from auxiliary circuit to main circuit safety insulation (IEC 60947-1/EN 50178) for operating voltages ≤ 300V AC
operating voltage 300V AC ... 500V AC (IEC 60947-1)
safety insulation (EN 50178), suitable for working voltage 300 ... 500V AC
control input and control supply voltage to auxiliary circuits safety insulation (IEC 60947-1),≤ 300V AC in auxiliary circuits
safety insulation (EN 50178), in auxiliary circuits ≤ 300V AC

control
Enter Name Control Input
Rated operating voltage UC 230V AC
Trigger voltage range 85V AC ... 253V AC
Rated operating current IC 7 mA (input type 1)
mains frequency 50Hz 60Hz 50/60Hz
Switch Threshold 44V AC ("0" signal)
85V AC ("1" signal)
switch level < 5V AC (for emergency stop)
Typical closing time < 70 ms

AC output
Rated operating voltage Ue 500V AC
Operating voltage range 42V AC ... 550V AC
Rated operating current Ie 2.4 A (AC-51)
2.4 A (AC-53a)
mains frequency 50/60Hz
Load current range 180 mA ... 2.4 A (see decay curve)
action characteristics according to IEC 60947-4-2 Class 10A
cooling time 20 min (for automatic reset)
leakage current 0 mA
protection circuit surge protection
Confirm Output
Considerations confirmation: floating transfer contact, signal contact
Contact Type 1 changeover contact
switching capacity according to IEC 60947-5-1 3 A (230 V, AC15)
2 A (24V (DC13))

control loop
Connection Mode screw connection
stripping length 8mm
thread M3
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load Circuit
Connection Mode screw connection
stripping length 8mm
thread M3
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
2900421

Phoenix ELR H3-IES-SC-230AC/500AC-2-Hybrid Motor Starter 2900568