Phoenix PLT-SEC-T3-24-FM-UT-3 class surge protection device 2907916, type 3 surge protection, including protective connectors and base elements, built-in status indicators and remote signaling for single-phase power networks. Rated voltage: 24V AC/DC

Product Type Equipment Protection
product series SEC Family
IEC power supply system TN-S
type DIN rail module, split, detachable
Bits 2
Surge protection fault alarm visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category III
pollution level 2
IEC Category III
T3
EN Type T3
Ports One

indicator/remote signaling
Connection Name Remote alarm contact
switching function changeover contact
Nominal operating voltage 250V AC
125V DC (200 mA DC)
working current 0.5 A AC
0.5 A DC (75V DC)

Connection Mode screw connection
thread M3
Tightening torque 0.5 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.7mm
height 93.4mm
depth 74.5mm (7.5mm with DIN rail)
Horizontal stitch pitch 1 Partition

color (pin connector) light gray (RAL 7035)
color (basic element) gray (RAL 7042)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6-FR 20 % GF
PA 6.6-FR
Shell Material PA 6.6-FR 20 % GF
PA 6.6-FR

protection channel L-N
L-PE
N-PE
movement direction 1L-N & N-PE
Rated voltage UN 24V AC (TN-S)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous voltage Uc 34V AC
Rated load current IL 26 A (at 30°C)
Residual Flow IPE ≤ 5 µA
Standby power consumption PC ≤ 2.7 mVA (UREF)
≤ 4.8 mVA (UC)
Reference test voltage UREF 27V AC
Nominal discharge current In(8/20)µs 1 kA
Combined surge UOC 2 kV
voltage protection level Up(L-N) ≤ 0.2 kV
voltage protection level Up(L-PE) ≤ 0.6 kV
voltage protection level Up(N-PE) ≤ 0.6 kV
UT(L-N) 50V AC (120 min/tolerance mode)
UT(L-PE) 50V AC (120 min/tolerance mode)
response time tA(L-N) ≤ 25 ns
response time tA(L-PEN) ≤ 100 ns
response time tA(N-PE) ≤ 100 ns
Rated short-circuit current ISCCR 10 kA AC
maximum spare fuse with branch wiring 32 A (gG / B / C)
Additional technical data
Rated short-circuit current ISCCR 0.25 kA DC (no additional spare fuse in the DC branch)
5 kA DC (for 20 A gG/B back-up protection fuses)
Maximum discharge current Imax(8/20) µs 4 kA
Nominal discharge current In(8/20) µs 3 kA
2907916

Phoenix Class PLT-SEC-T3-24-FM-UT-3 Surge Protective Equipment 2907916