Phoenix PLT-SEC-T3-BE-FM-UT-3 surge protector base 2907924, base element, used for PLT-SEC with remote indication contacts-...-protective connector of UT/PT product series.
| Product Type | basic elements |
| Product Series | SEC Family |
| IEC power supply system | TN-S |
| TT | |
| type | DIN rail module, split, detachable |
| Bits | 2 |
| Surge protection fault alarm | Remote communication contact |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| IEC Category | II / III |
| T2 / T3 | |
| EN Type | T2 / T3 |
| Ports | One |
| indicator/remote signaling | |
| Connection Name | Remote alarm contact |
| switching function | changeover contact |
| Nominal operating voltage | 250V AC |
| 125V DC (200 mA DC) | |
| working current | 0.5 A AC |
| 0.5 A DC (75V DC) | |
| Connection Mode | screw connection |
| thread | M3 |
| Tightening torque | 0.5 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 17.7mm |
| height | 93.4mm |
| depth | 51.5mm (7.5mm with DIN rail) |
| Horizontal stitch pitch | 1 Partition |
| color (pin connector) | light gray (RAL 7035) |
| color (basic element) | gray (RAL 7042) |
| flame retardant rating, according to UL 94 | V-0 |
| material | 600 |
| insulation material | PA 6.6-FR 20 % GF |
| PA 6.6-FR | |
| Shell Material | PA 6.6-FR 20 % GF |
| PA 6.6-FR |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | 1L-N & N-PE |
| Rated voltage UN | 240V AC (TN-S) |
| 240V AC (TT) | |
| Rated frequency fN | 50Hz (60 Hz) |
| Maximum continuous voltage Uc | 264V AC |
| Rated load current IL | 26 A (at 30°C) |
| Rated short-circuit current ISCCR | 10 kA AC |
| maximum spare fuse with branch wiring | depends on the plug used |