Phoenix ELR H5-IES-SC-230AC/500AC-2-hybrid motor starter 2900420, hybrid motor starter, used for reverse starting three-phase AC motors, up to 500V AC,2.4 A output current, 230V AC control voltage, adjustable overload Break and emergency stop function to SIL 3/PL e
Product Type
hybrid motor starter
product series
CONTACTRON
Mode of operation
100% operating factor
phase number
3
Motor Starter Type
reversible starter
Switching frequency
≤ 2Hz (depending on load)
rated conditions
2.2W
Switching frequency
≤ 2Hz (depending on load)
maximum power loss
4.7W
minimum power loss
2.6W
type of coordination
1
Power
Rated control circuit supply voltage US
230V AC
Control Supply Voltage Range
85V AC ... 253V AC
Rated control supply current IS
4 mA
mains frequency
50/60Hz
protection circuit
surge protection
insulation characteristics
Rated insulation voltage
500V
Rated overvoltage
4 kV
Overvoltage Level
III
pollution level
2
control input and control supply voltage and insulation characteristics from auxiliary circuit to main circuit
safety insulation (IEC 60947-1/EN 50178) for operating voltages ≤ 300V AC
operating voltage 300V AC ... 500V AC (IEC 60947-1)
safety insulation (EN 50178), suitable for working voltage 300 ... 500V AC
control input and control supply voltage to auxiliary circuits
safety insulation (IEC 60947-1),≤ 300V AC in auxiliary circuits
safety insulation (EN 50178), in auxiliary circuits ≤ 300V AC
control
Enter Name
Control Input Right/Left
Rated operating voltage UC
230V AC
Trigger voltage range
85V AC ... 253V AC
Rated operating current IC
7 mA (input type 1)
mains frequency
50Hz 60Hz 50/60Hz
Switch Threshold
44V AC ("0" signal)
85V AC ("1" signal)
switch level
< 5V AC (for emergency stop)
Typical closing time
< 70 ms
AC output
Rated operating voltage Ue
500V AC
Operating voltage range
42V AC ... 550V AC
Rated operating current Ie
2.4 A (AC-51)
2.4 A (AC-53a)
mains frequency
50/60Hz
Load current range
180 mA ... 2.4 A (see decay curve)
action characteristics according to IEC 60947-4-2
Class 10A
cooling time
20 min (for automatic reset)
leakage current
0 mA
protection circuit
surge protection
Confirm Output
Considerations
confirmation: floating transfer contact, signal contact
Contact Type
1 changeover contact
switching capacity according to IEC 60947-5-1
3 A (230 V, AC15)
2 A (24V (DC13))
control loop
Connection Mode
screw connection
stripping length
8mm
thread
M3
Rigid conductor cross section
0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load Circuit
Connection Mode
screw connection
stripping length
8mm
thread
M3
Rigid conductor cross section
0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
2900421
넳넲
Phoenix ELR H5-IES-SC-230AC/500AC-2-Hybrid Motor Starter 2900420