Phoenix ELR W3- 24DC/500AC- 9I-BR-hybrid motor starter 2900795, hybrid motor starter, used for commutation starting 3-phase AC motors up to 550V AC, 24V DC input, 9 A output current, providing adjustable overload breaking and phase fault detection functions.
| Product Type | hybrid motor starter |
| Product Series | CONTACTRON |
| phase number | 3 |
| Motor Starter Type | reversible starter |
| Switching frequency | ≤ 2Hz (depending on load) |
| Switching frequency | ≤ 2Hz (depending on load) |
| maximum power loss | 14.6W |
| minimum power loss | 1.1W |
| Power | |
| Rated control circuit supply voltage US | 24V DC |
| Control Supply Voltage Range | 19.2V DC ... 30V DC |
| Rated control supply current IS | 40 mA |
| protection circuit | surge protection |
| polarity protection | |
| insulation characteristics | |
| Rated insulation voltage | 500V |
| Rated overvoltage | 6 kV |
| Overvoltage Level | III |
| pollution level | 2 |
| control input and control supply voltage and insulation characteristics from auxiliary circuit to main circuit | safety insulation (IEC 60947-1) for operating voltages ≤ 300V AC |
| operating voltage 300V AC ... 500V AC (IEC 60947-1) | |
| safety insulation (IEC 60947-1),≤ 300V AC in auxiliary circuits | |
| control | |
| Enter Name | Control Input Right/Left |
| Rated operating voltage UC | 24V DC |
| Trigger voltage range | 19.2V DC ... 30V DC |
| Rated operating current IC | 5 mA (input type 1) |
| Switch Threshold | 9.6V ("0" signal) |
| 19.2V ("1" signal) | |
| Typical Response Time | < 35 ms |
| Typical closing time | < 40 ms |
| protection circuit | polarity protection |
| AC output | |
| Rated operating voltage Ue | 500V AC |
| Operating voltage range | 42V AC ... 550V AC |
| Rated operating current Ie | 9 A (AC-51) |
| 6.5 A (AC-53a) | |
| mains frequency | 50/60Hz |
| Load current range | 1.5 A ... 9 A (see decay curve) |
| action characteristics according to IEC 60947-4-2 | Class 10A |
| cooling time | 20 min (for automatic reset) |
| leakage current | 0 mA |
| protection circuit | surge protection |
| Confirm Output | |
| Considerations | Confirmation 01: Floating Transfer Contact |
| Contact Type | 1 changeover contact |
| switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
| 2 A (24V (DC13)) | |
| control loop | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 2.5 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| 5 lbf-in. ... 7 lbf-in. | |
| Load Circuit | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 2.5 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| 5 lbf-in. ... 7 lbf-in. | |
| Status Display | LED (yellow) |
| Operating voltage display | Green LED |
| error indication | Red LED |