Phoenix FL COMSERVER UNI 232/422/485-interface converter 2313452, second generation FL COMSERVER UNI..., serial device server, used to switch 232/422/485 serial ports to Ethernet, only supports TCP,UDP,Modbus gateway and PPP applications, including CD-ROM with COM port conversion software and user files

Product Type Interface Interface Converter
Application TCP, UDP, Modbus Gateway, PPP
MTTF 2013 Number (SN 29500 Standard, Temperature 25°C, Duty Cycle 21%)
879 years (SN 29500 standard, temperature 40°C, duty cycle 34.25%)
359 years (SN 29500 standard, temperature 40°C, duty cycle 100%)
MTBF 666 years (Telcordia standard, temperature 25°C,21% operation cycle (5 days a week, 8 hours a day))
179 years (Telcordia standard, 40°C,34.25% cycle (5 days a week, 12 hours a day))

Modbus/TCP-Client
the number of Modbus/TCP clients 8
System Requirements
Supported Browsers Netscape Communicator 4.5 and later or Internet Explorer V5.5 and later

electrical isolation VCC // Ethernet // Serial
rated conditions 2.4W
test voltage data interface/data interface 1.5 kVrms(50 Hz,1 min)
test voltage data interface/power supply 1.5 kVrms(50 Hz,1 min)
Power
Supply Voltage Range 19.2V AC/DC ... 28.8V AC/DC (via plug-in COMBICON screw terminal blocks)
22.8V DC ... 25.2V DC (as backup or redundant, power supply via backplane bus contacts and system current)
Typical current consumption 100 mA (24V DC)
Function
Management Web-based management, SNMP, emergency exit with Telnet and serial interface
diagnostics and status indicators LEDs: UL (logic level),TD + RD (data activation serial number),FD (full duplex),100(100Mbps mode), link (Ethernet), active (Ethernet),ERR (fault)

Power
single wire/wiring point, rigid 0.2 mm² ... 2.5 mm²
single wire/wiring point, flexible 0.2 mm² ... 2.5 mm²
stripping length 7.00mm
Tightening torque 0.5 Nm ... 0.6 Nm

signal Ethernet
Modbus
Web Server is
data: Ethernet interface, 10/100Base-T(X), compliant with IEEE 802.3
serial transmission rate 10/100 Mbps, adaptive
Connection Mode RJ45 Hole Connector, Shielded
Channels 1
Transmission Length ≤ 100 m (shielded twisted pair)
Supported Protocols TCP/IP,UDP,Modbus(TCP,RTU/ASCII),PPP
Auxiliary Agreement ARP, DHCP, BOOTP, SNMP, RIP, RARP, HTTP, TFTP, ICMP
Data Flow Control/Protocol Modbus/TCP
data: RS-232 interface, according to ITU-T V.28, EIA/TIA-232, DIN 66259-1
serial transmission rate 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4 kbps
Connection Mode D-SUB-9 male connector
Tightening torque 0.4 Nm
Pin Distribution DTE/DCE switching via network-based management
Transmission Length 15 m
File Format/Encoding UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity
Data Flow Control/Protocol software handshake program, Xon/Xoff, or hardware handshake RTS/CTS // 3964 R compatible, Modbus RTU/ASCII
data: RS-422 interface according to ITU-T V.11,EIA/TIA-422,DIN 66348-1
serial transmission rate 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4; 500; 1000 kbps
Connection Mode COMBICON in-line/screw connection
Transmission Length ≤ 1200 m
terminal resistance 390 Ω (configurable)
180 Ω
390 Ω
File Format/Encoding UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity
Data Flow Control/Protocol automatic control
data: RS-485 interface, according to EIA/TIA-485, DIN 66259-4/RS-485 2-wire
serial transmission rate 0.3; 0.6; 1.2; 2.4; 4.8; 7.2; 9.6; 19.2; 38.4; 57.6; 115.2; 187.5; 230.4; 500; 1000 kbps
Connection Mode COMBICON in-line/screw connection
terminal resistance 390 Ω
180 Ω
390 Ω (configurable)
File Format/Encoding UART/NRZ: 7/8 Bit Data, 1/2 Bit Stopp, None/Even/Odd Parity
Data Flow Control/Protocol automatic control

width 22.5mm
height 99mm
depth 116mm

color (shell) Green (RAL 6021)
Identification Material (Shell) PA 6.6-FR