Phoenix PSR-SPP- 24UC/URM/3X1/3X2-coupling relay 2981842, safety coupling relay, with mechanical interlocking contacts, 3 normally open contacts, 3 normally closed contacts, pluggable in-line terminal, Width: 22.5mm

Product Type coupling relay
Product Series PSRclassic
Application Safety Shutdown
high requirements
low requirements
control Single and Dual Channel
mechanical life 10x 106Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
restart time < 1 s (start-up time)

rated conditions 6.11W (in UB= 26.4V DC,US= 24 V, IS= 45 mA,n = 1, IL² = 48 A²,Rcontact= When 0.1,)
Rated operating mode 100% Eligible
Rated insulation voltage 250V
rated overvoltage/insulation 4kV/basic safety isolation (6kV enhanced safety isolation between input loop and normally open safety contact output.)
Power
Rated control circuit supply voltage US 20.4V AC/DC ... 26.4V AC/DC

Overview
Rated control circuit supply voltage US 24V AC/DC -15 % / +10%
US Typical 1.08W
Rated control supply current IS Typical 45 mA
Input Voltage Range 20.4V AC/DC ... 26.4V AC/DC
Impulse current Typical 350 mA DC (& Delta;t < 1 & micro;s Us)
Typical 350 mA AC (& Delta;t = 2 ms Us)
Typical startup time (Us) Typical 15 ms (when controlled via A1)
Typical Release Time Typical 15 ms (when controlled via A1)
Recovery Time < 500 ms
Maximum switching frequency 0.5Hz
protection circuit Surge protection; Suppressor diode
Operating voltage display 1 x LED (green)

Contact Type 3 normally open safety contact outputs
3 fault diagnosis output contacts
Contact Material AgSnO2
maximum switching voltage 230V AC/DC (note load curve)
Minimum Switching Voltage 5V AC/DC
limit continuous current 6 A (N/O contact)
6 A (normally closed contact)
Maximum impact current 8 A
Minimum impulse current 10 mA
the square of the total current value 48 A2
Maximum power rating (resistive load) more values, see Load Curve
Maximum power rating (inductive load) 48W (normally open contact, 24V DC, & tau; = 40 ms)
40W (normally open contact, 48V DC, & tau; = 40 ms)
36W (normally open contact, 60V DC, & tau; = 40 ms)
35W (normally open contact, 110V DC, & tau; = 40 ms)
33W (normally open contact, 220V DC, & tau; = 40 ms)
On-Off Capacity 50 mW minimum
output fuse 10 A gL/gG (N/O contact)
4 A gL/gG (normally open contact for low demand applications)
6 A gL/gG (normally closed contact)
2900509

Phoenix PSR-SPP- 24UC/URM/3X1/3X2-coupling relay 2981842

Product Center

PRODUCT CENTER