Phoenix PSR-SPP-24UC/ESAM4/8X1/1X2-safety relay 2963996, safety relay, used for emergency stop and safety door monitoring, safety level up to EN ISO 13849 standard SIL 3 or Cat. 4, PL e, single channel or dual Channel operation, 8 active current paths, US = 24V DC, pluggable in-line terminal

Product Type safety relay
Product Series PSRclassic
Application Emergency stop button
safety door
control Single and Dual Channel
mechanical life about 107Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2

rated conditions 31.7W (US= 26.4 V, IL² = 144 A²,PTotal max= 2.9W +28.8 W)
Rated operating mode 100% Eligible
Rated insulation voltage 250V
rated overvoltage/insulation 4 kV foundation safety isolation:
Between all current paths and housing
6 kV reinforced isolation withstand voltage:
Between A1/A2 and 63/64, 73/74, 83/84
Between S10/S11/S12/S33/S34/S35 and 63/64, 73/74, 83/84
Between 63/64, 73/74, 83/84

Overview
Rated control circuit supply voltage US 24V DC -15 % / +10%
US Typical 2.4W (DC)
Rated control supply current IS typical 100 mA DC (US)
Impulse current 3.5 A (Δt = 2 ms Us)
Max 150 mA (& Delta;t = 1 ms,Us/Ix)
Max 200 mA (& Delta;t = 1 ms,Us/Ix)
max -180 mA (& Delta;t = 1 ms,Us/Ix)
< 10 mA (Us/Ixto S34)
< 10 mA (Us/Ixto S35)
power consumption 50 mA (Us/Ixto S10)
50 mA (Us/Ixto S12)
-50 mA (Us/Ixto S22)
0 mA (Us/Ixto S34)
1 mA (Us/Ixto S35)
input/start and feedback circuits 24V DC -15 % / +10%
filter time 2 ms (at A1, at the voltage dip Us)
max. 1.5 ms (at S10, S12; test pulse width)
7.5 ms (at S10, S12; test pulse rate)
test pulse rate = 5 x test pulse width
Typical Response Time < 120 ms (auto start)
< 140 ms (manual reset)
Typical startup time (Us) < 200 ms (when controlled via A1)
Typical release time < 20 ms (when controlled by s11/S12 and S21/S22)
< 50 ms (when controlled via A1)
parallel
Recovery Time < 500 ms (meets the requirements of safety functions)
< 1 s (start-up time)
Maximum switching frequency 0.5Hz
protection circuit Surge protection; Suppressor diode
Allowable total conductor resistance 11 Ω (input sensor circuit S10, S12, S22)
50Ω (S34,S35 start circuit input)
Operating voltage display 1 x LED (green)
Status Display 2 x LED (green)

Contact Type 8 normally open safety contact outputs
1 signal transmission current path
Contact Material AgSnO2
maximum switching voltage 250V AC/DC
Minimum Switching Voltage 5V AC/DC
limit continuous current 6 A
Maximum impact current 6 A
Minimum impulse current 10 mA
the square of the total current value 144 A2(normally open safety contact output)
36 A2(signal transmission current path)
Minimum on-off capacity 50 mW
output fuse 10 A gL/gG (normally open safety contact output)
6 A gL/gG (signal transmission current path)

connection technology
pluggable is
2981428

Phoenix PSR-SPP-24UC/ESAM4/8X1/1X2-Safety Relay 2963996

Product Center

PRODUCT CENTER