Phoenix CN-LAMBDA/4-5.9-SB-surge protector 2800023, the adapter adopts Lambda/4 surge protection technology for the protection of coaxial signal interface. Connection: N type pin connector/hole connector
| Product Type | Transceiver System |
| IEC Category | C2 |
| C3 | |
| D1 | |
| VDE requirement level | C2 |
| C3 | |
| D1 | |
| type | Protection Adapter |
| Surge protection fault alarm | None |
| Connection Mode | Type-N connector, 50 Ω |
| Tightening torque | 1.4 Nm ... 1.7 Nm (N coupling nut) |
| Dimensional drawing | |
| width | 26.1mm |
| height | 38mm |
| depth | 65mm |
| color | NICKEL |
| sealing material | silicon |
| Shell Material | brass (copper zinc alloy) |
| Shell surface material | Ni |
| Core Material | BeCu |
| Core Surface Material | gold |
| Insulator Material | PTFE |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Shield/Earth Ground |
| Rated current | 5 A (25 °C) |
| Rated discharge current In(8/20)& micro;s (core-ground) | 50 kA |
| Nominal discharge current In(8/20)& micro;s (core/shield) | 50 kA |
| pulse discharge current Iimp(10/350) µs | 20 kA |
| pulse discharge current Iimp(350) & micro;s (core-ground) | 20 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) | 60 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-shield) | 60 kA |
| impulse current (10/350) & micro;s (L-N), peak current Iimp | 20 kA |
| voltage protection level Up(line-ground) | ≤ 11V (6 kV / 3 kA) |
| voltage protection level Up(core-shield) | ≤ 11V (6 kV / 3 kA) |
| input attenuation AE, asymmetric. | Typical 0.15 dB (≤ 0.25 dB) |
| Frequency Range | 2.4 GHz ... 7.6 GHz |
| 50 Ω system | Typical 1.10 (2.4 GHz ... 5.9 GHz) |
| ≤ 1.20 (2.4 GHz ... 7.6 GHz) | |
| Allowable high-frequency power Pmax,VSWR = xx(50 ohm system) | ≤ 500W |
| ≤ 4 kW (peak) | |
| Surge protection fault alarm | None |
| Impact resistance (line-ground) | C2 - 10 kV / 5 kA |
| D1 - 2.5 kA | |
| Impact resistance (line-shield) | C2 - 10 kV/5 kA |
| D1 - 2.5 kA |
| environmental conditions | |
| protection level | IP68 (24 h / 1 m) |
| ambient temperature (operation) | -40°C ... 90°C |
| Conformance/Certification | |
| FCC | Part 15, Part 90 |