Phoenix PT 4-12DC-ST-Surge Protector-Plug and unplug 2839237, protection plug PT, used for protection of 4-wire floating ground signal circuit. Rated voltage: 12V DC

Product Type measurement and control technology
Product Series PLUGTRAB PT
IEC Category C1
C2
C3
D1
VDE requirement level C1
C2
C3
D1
type needle type
Surge protection fault alarm None
can test protectors using the CHECKMASTER software tests:
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 12V DC

Connection Mode screw connection (connection to the base)
thread M3
Tightening torque 0.5 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.7mm
height 45mm
depth 52mm
Horizontal stitch pitch 1 Partition
full module width 17.7mm
Full module height 90mm
full module depth 65.5mm

color black (RAL 9005)
COPPER
flame retardant rating, according to UL 94 V-0
Shell Material PA 6.6

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous operating voltage UC 12.8V DC
9V AC
Rated current 2 A (80 °C)
UC, the effective working current IC ≤ 1 mA
Residual Flow IPE ≤ 4 & micro;A (direct grounding)
≤ 1 & micro;A (with PT 4 F-BE)
Nominal discharge current In(8/20) & micro;s (core-core) 690 A
Rated discharge current In(8/20)& micro;s (core-ground) 10 kA
pulse discharge current Iimp(10/350) µs 2.5 kA (per path)
Total discharge current ITotal(8/20) µs 20 kA
Maximum discharge current Imax(8/20) & micro;s (core-core) 690 A
Maximum discharge current Imax(8/20) & micro;s (core-ground) 10 kA
rated power pulse current lan (1000)& micro;s (core-core) 128 A
Output voltage limit 1 kV/& micro;s (core-to-core) peak ≤ 20V
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 450V
≤ 1 kV (with PT 4 F-BE)
Output voltage limit 1 kV/& micro;s (core-core) static ≤ 18V
Residual voltage ln,(wire-wire) ≤ 50V
Residual voltage lan(10/1000)& micro;s (wire-wire) ≤ 25V
voltage protection level Up(core-core) ≤ 40V (C1 - 1 kV / 500 A)
voltage protection level Up(line-ground) ≤ 450V
≤ 1 kV (with PT 4 F-BE)
response time tA(core-core) ≤ 1 ns
response time tA (core-ground) ≤ 100 ns
response time tA (line-signal ground) ≤ 1 ns
2838254

Phoenix PT 4-12DC-ST-Surge Protector-Plug and Plug 2839237