Phoenix RAD-AO4-IFS-I/O expansion module 2901538, Radioline-I/O expansion module, 4 analog current or voltage outputs (0/4 mA ... 20 mA, 0V ... 10V)

Product Type Expansion Module
MTTF 999 years (SN 29500 standard, temperature 25°C, duty cycle 21%)
404 years (SN 29500 standard, temperature 40°C, duty cycle 34.25%)
156 years (SN 29500 standard, temperature 40°C, duty cycle 100%)
insulation characteristics
Overvoltage Category II
pollution level 2

Rated insulation voltage 60V (conforming to EN/IEC 60079-7)
electrical isolation 50V (rated insulation voltage (between analog output/TBUS power supply, enhanced insulation in accordance with EN 61010))
300V (rated insulation voltage (base isolation from adjacent equipment according to EN/IEC 61010))
Test voltage for analog I/O 1.5 kV AC (50 Hz,1 min)
rated conditions 2.76W
Transient overvoltage protection is
Power
Supply Voltage Range 19.2V DC ... 30.5V DC (DIN rail connector)
Maximum current consumption ≤ 115 mA (at 24V DC(25°C))

simulation
Output Name analog output
outputs 4
voltage output signal 0V ... 10V
Maximum voltage output signal ~ 10.83V
current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Maximum current output signal ~ 21.67 mA
load ≥ 10 kΩ
≤ 500 Ω
resolution 16 bits
accuracy ≤ 0.02 % (at 25°C)
Typical 0.5 % (voltage output)
temperature coefficient, typical Typical 0.0025 %/K at -40°C ... +70°C
protection circuit output

Tightening torque 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Connection Mode screw connection
stripping length 7mm
Minimum cross section of rigid conductor 0.2 mm²
Maximum cross section of rigid conductor 2.5 mm²
flexible lead 0.2 mm²
flexible conductor 2.5 mm²
Minimum Wire Cross Section AWG 24
Maximum conductor cross section AWG 14

Status Display LED power supply, PWR (green)
Green LED (Bus Communication, DAT)
LED peripheral fault, ERR (red)

Dimensional drawing
width 17.5mm
height 113mm
depth 114.5mm

color (shell) gray (RAL 7042)
Identification Material (Shell) PA 6.6-FR
flame retardant rating, according to UL 94 V0

environmental conditions
protection level IP20
ambient temperature (operation) -40°C ... 70°C (>55°C attenuation, see technical documentation)
-40 °F ... 158 °F (>131 °F attenuation, see technical documentation)
ambient temperature (storage/transport) -40°C ... 85°C
-40 °F ... 185 °F
elevation 2000 m
Allowable humidity (operating) 20%... 85%
Allowable humidity (storage/transportation) 20%... 85%
Impact 16g,11 ms
vibration (operation) Complies with IEC 60068-2-6: 5g,10Hz ... 150Hz