Phoenix PT 2X2-5DC-ST-Surge Protector-Plug-in 2838241,PT protection plug, with protection circuit, used for two 2-wire floating ground signal circuits. 5V DC rated voltage. HART Compatible.

Product Type measurement and control technology
Product Series PLUGTRAB PT
IEC Category C1
C2
C3
D1
type needle type
Surge protection fault alarm None
can test protectors using the CHECKMASTER software tests:
line pairs per module 2
insulation characteristics
Overvoltage Category III

Rated voltage UN 5V DC

Connection Mode screw connection (connection to the base)
thread M3
Tightening torque 0.8 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.5mm
height 44.8mm
depth 51.7mm
Horizontal stitch pitch 1 Division
full module width 17.7mm
Full module height 90mm
full module depth 65.5mm

color black (RAL 9005)
COPPER
flame retardant rating to UL 94 V-0
Shell Material PA 6.6

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous operating voltage UC 6V DC
4V AC
Rated current 450 mA (45°C)
UC, the effective working current IC ≤ 1 mA
Residual Flow IPE ≤ 1 & micro;A (applicable to PT 2X2 F-BE)
≤ 4 µA
Nominal discharge current In(8/20) & micro;s (core-core) 10 kA
Rated discharge current In(8/20)& micro;s (core-ground) 10 kA
pulse discharge current Iimp(10/350) µs 2.5 kA (per path)
Total discharge current ITotal(8/20) µs 20 kA
Maximum discharge current Imax(8/20) & micro;s (core-core) 10 kA
Maximum discharge current Imax(8/20) & micro;s (core-ground) 10 kA
Output voltage limit 1 kV/& micro;s (core-to-core) peak ≤ 12V
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 450V
Output voltage limit 1 kV/& micro;s (core-core) static ≤ 10V
Residual voltage ln,(wire-wire) ≤ 10V
In(line-signal ground) ≤ 450V
Residual voltage lan(10/1000)& micro;s (wire-wire) ≤ 12V
response time tA(core-core) ≤ 1 ns
response time tA (core-ground) ≤ 100 ns
input attenuation AE, symmetric. 0.5 dB (≤ 200 kHz)
cut-off frequency fg(3 dB),50 Ω symmetric system Typical 1 MHz
capacitance (core-core) 6 nF
the resistance of each path 2.2 Ω
Surge protection fault alarm None
Impact tolerance (line-line) C2 - 10 kV / 5 kA
Impact resistance (line-ground) C2 - 10 kV / 5 kA
D1 - 2.5 kA
2838254

Phoenix PT 2X2-5DC-ST-Surge Protector-Plug and Plug 2838241