Phoenix SP-EE-TT-6-1X2-24DC-UT-surge protector 1445846, surge protection, used for 2-wire floating signal circuit, such as 0(4) ... 20 mA current circuit, HART compatible.

Product Type measurement and control technology
IEC Category C1
C2
C3
D1
type rail mounting module, monolithic
line pairs per module 1
insulation characteristics
Overvoltage Category III

Rated voltage UN 24V DC

Connection Mode screw connection
thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 6.2mm +0.1mm
height 105.8mm
depth 69.5mm (7.5mm with DIN rail)

color Traffic Grey B (RAL 7043)
flame retardant rating, according to UL 94 V-0
insulation material PBT
Shell Material PBT

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous operating voltage UC 30V DC
21V AC
Rated current 500 mA (40°C)
UC, the effective working current IC ≤ 5 µA
Residual Flow IPE ≤ 1 µA
Nominal discharge current In(8/20) & micro;s (core-core) 5 kA
Rated discharge current In(8/20)& micro;s (core-ground) 5 kA
pulse discharge current Iimp(350) & micro;s (core-core) 0.5 kA
pulse discharge current Iimp(350) & micro;s (core-ground) 0.5 kA
Total discharge current ITotal(8/20) µs 10 kA
voltage protection level Up(core-core) ≤ 55V (C1 - 1 kV / 500 A)
≤ 65V (C2 - 10 kV / 5 kA)
≤ 50V (C3 - 25 A)
≤ 55V (C3 - 100 A)
voltage protection level Up(line-ground) ≤ 750V (C1 - 1 kV / 500 A)
≤ 750V (C2 - 10 kV / 5 kA)
≤ 700V (C3 - 25 A)
≤ 750V (C3 - 100 A)
voltage protection level Upstatic (core-core) ≤ 50V (C1 - 1 kV / 500 A)
≤ 65V (C2 - 10 kV / 5 kA)
voltage protection level Upstatic (core-ground) ≤ 750V (C1 - 1 kV / 500 A)
≤ 750V (C2 - 10 kV / 5 kA)
response time tA(core-core) ≤ 1 ns
response time tA (core-ground) ≤ 100 ns
input attenuation AE, symmetric. Typical 0.3 dB (≤ 250 kHz / 150 Ω)
cut-off frequency fg(3 dB),150 Ω symmetric system Typical 940 kHz
capacitance (core-core) Typical 2.2 nF
the resistance of each path 1.65 Ω ± 20%
Surge protection fault alarm None
630 mA (FF)
Impact tolerance (line-line) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impact resistance (line-ground) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
pulse reset time (lead-lead) ≤ 700 ms
pulse reset time (lead-ground) ≤ 1500 ms
1445846

Phoenix SP-EE-TT-6-1X2-24DC-UT-Surge Protector 1445846

Product Center

PRODUCT CENTER