Phoenix RAD-DAIO6-IFS-I/O expansion module 2901533, Radioline-I/O expansion module, 2 digital inputs and outputs (0 ... 250V AC/DC) and 1 analog input (0/4 ... 20 mA) and output (0/4 ... 20 mA,0 ... 10V)
Product Type
Expansion Module
MTTF
889 years (SN 29500 standard, temperature 25°C, duty cycle 21%)
391 years (SN 29500 standard, temperature 40°C, duty cycle 34.25%)
151 years (SN 29500 standard, temperature 40°C, duty cycle 100%)
insulation characteristics
Overvoltage Category
II
pollution level
2
electrical isolation
300V (rated insulation voltage (in all cases refers to enhanced insulation between digital input/digital output/TBUS power supply, in accordance with EN/IEC 61010))
50V (rated insulation voltage (in all cases between analog input/analog output/TBUS power supply, reinforced insulation according to EN/IEC 61010))
300V (rated insulation voltage (in all cases refers to the enhanced insulation between digital input and output // analog input and output, in accordance with EN/IEC 61010))
300V (rated insulation voltage (base isolation from adjacent equipment according to EN/IEC 61010))
Test Voltage for Digital I/O
2.5 kV AC (50 Hz,1 min)
Test voltage for analog I/O
1.5 kV AC (50 Hz,1 min)
rated conditions
2.28W
Transient overvoltage protection
is
power supply
Supply Voltage Range
19.2V DC ... 30.5V DC (DIN rail connector)
Maximum current consumption
≤ 95 mA (at 24V DC(25°C))
digital quantity
Maximum current consumption
< 1 mA
simulation
Input Description
Analog Input
Input Number
1
current input signal
0 mA ... 20 mA (settable via DIP switch)
4 mA ... 20 mA (settable via DIP switch)
Maximum current input signal
22 mA
input current
< 70 Ω
resolution
16 Bit
accuracy
≤ 0.02 % (at 25°C)
protection circuit
Short circuit and overload protection
temperature coefficient, typical
Typical 0.0025 %/K at -40°C ... +70°C
supply voltage
12V DC (UANAvia terminal block PWR1,+ I1 for passive sensors, 25 mA)