Phoenix PT 2X1VA-120AC-ST-surge protector-plug-in 2839185, protection plug PT, used for high-voltage signal protection, dual channel, optical fault alarm. Rated voltage: 120V AC

Product Type measurement and control technology
Product Series PLUGTRAB PT
IEC Category C1
C2
C3
D1
type needle type
can test protectors using the CHECKMASTER software tests:
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 120V AC (50/60 Hz)
indicator/remote signaling
switching function normally closed contact

Connection Mode screw connection (connection to the base)
thread M3
Tightening torque 0.5 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.5mm
height 44.8mm
depth 51.7mm
Horizontal stitch pitch 1 Partition
full module width 17.7mm
Full module height 90mm
full module depth 65.5mm

color black (RAL 9005)
COPPER
flame retardant rating, according to UL 94 V-0
Shell Material PA 6.6

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Earth Ground
Maximum continuous operating voltage UC 150V DC
150V AC (50/60 Hz)
Rated current 26 A AC (30 °C)
1 A DC (82 °C)
UC, the effective working current IC ≤ 1.5 mA AC
≤ 2 mA DC
Residual Flow IPE ≤ 3 mA AC
≤ 4 mA DC
Rated discharge current In(8/20)& micro;s (core-ground) 2.5 kA
pulse discharge current Iimp(10/350) µs 500 A
Total discharge current ITotal(8/20) µs 5 kA
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 380V
Output voltage limit 1 kV/& micro;s (core-ground) static ≤ 380V
voltage protection level Up(line-ground) ≤ 450V (C1 - 1.4 kV / 0.7 kA)
≤ 550V (C2 - 5 kV/2,5 kA)
≤ 400V (C3 - 100 A)
response time tA (core-ground) ≤ 25 ns
input attenuation AE, asymmetric. Typical 0.3 dB (≤ 300 kHz / 150 Ω)
cutoff frequency fg(3 dB), asymmetric. 150 Ω in the system (signal ground) Typical 1 MHz
capacitance (core-ground) Typical 2.5 nF
Surge protection fault alarm with visual status indication window
25 A AC (gL/gG)
1 A DC (T)
Impact resistance (line-ground) C1 - 1.4 kV / 0.7 kA
C2 - 5 kV / 2.5 kA
C3 - 100 A
D1 - 500 A
2880024

Phoenix PT 2X1VA-120AC-ST-Surge Protector-Plug and Plug 2839185

Product Center