Phoenix ESSENTIAL-PS/3AC/24DC/240W/EE-power 1018291,ESSENTIAL edition power supply, primary switch mode, for DIN rail installation, input: 3 phase, output: 24V DC/240W

AC operation
Rated input voltage range 2x / 3x 400V AC ... 500V AC
Input Voltage Range 3x 320V AC ... 575V AC
AC input voltage range 3x 320V AC ... 575V AC
2x 360V AC ... 575V AC (2-phase system)
Supply Voltage AC
Impulse current < 15 A
impulse current integral (I2t) 0.2 A2s
AC frequency range 45Hz ... 65Hz
grid buffer time > 20 ms (3x 400V AC)
power consumption 3x 0.6 A (400V AC)
3x 0.5 A (480V AC)
Rated power consumption 284.4 VA
protection circuit transient surge protection; varistor
power factor (cos phi) 0.59
Typical Response Time < 1 s
Allowable Spare Fuses B6 B10 B16
recommend use 6 A ... 16 A
PE discharge current < 3.5 mA

efficiency 88.5 % (at 400V AC and rated)
output characteristics U/ I
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 22.5V DC ... 29.5V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 10 A (UOUT= 24V DC)
Attenuation 55°C ... 70°C (2.5 %/K)
feedback voltage resistance 35V DC
output < 35V DC
Maximum capacitive load Unlimited
Active Current Limit about 15 a
control deviation <1% (load change, static 10%... 90%)
<2% (change of load, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 10 mVSS
Short-circuit protection is
output power 240W
peak switching voltage rated load < 30 mVSS
maximum no-load power consumption 7.5W
Maximum rated load power loss 34W
rise time < 2 ms (UOUT(10%... 90%))
and connect Yes, for redundancy and increased capacity
Concatenation is

Input
Connection Mode screw connection
Minimum cross section of rigid conductor 0.2 mm²
Maximum cross section of rigid conductor 2.5 mm²
Minimum cross section of flexible lead 0.2 mm²
Flexible lead maximum cross section 2.5 mm²
Minimum Wire Cross Section AWG 24
Maximum conductor cross section AWG 14
stripping length 9mm
thread M2,5
Minimum tightening torque 0.4 Nm
Maximum tightening torque 0.5 Nm
Output
Connection Mode screw connection
Minimum cross section of rigid conductor 0.2 mm²
Maximum cross section of rigid conductor 2.5 mm²
Minimum cross section of flexible lead 0.2 mm²
Flexible lead maximum cross section 2.5 mm²
Minimum Wire Cross Section AWG 16
Maximum conductor cross section AWG 12
stripping length 9mm
thread M2,5
Minimum tightening torque 0.4 Nm
Maximum tightening torque 0.5 Nm

Signal Type LED
Operating voltage display Green LED