Phoenix SCK-M-I-4S-20A-PV string monitoring module 2903242,SCK measurement module, used to monitor photovoltaic systems, 4 x current measurement (up to 20 A),1 x digital input, interface to SCK communication module

Product Type Current transmitter
Product Series SOLARCHECK
insulation characteristics
pollution level 2

protection circuit surge protection; 33V suppressor diode
Power
Supply Voltage Range via SOLARCHECK communication module
current self-loss 43 mA (typical)
50 mA (max)

signal: digital
Input Description Digital Input
valid input source Floating switch contact
Cable Length ≤ 30 m
measurement
Input Number 4
Input current range 0 A DC ... 20 A DC (UL: 0 A DC...25 A DC)
Reverse current detection -1 A DC ... 0 mA
LSB: Current 20 mA
Overload 5 x IN
temperature coefficient, typical 0.02 %/K (TK20)
Maximum transmission error ± 1% (from end of set range)

Connection Mode screw connection
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12
Tightening torque 0.5 Nm ... 0.6 Nm

data: SCK-C-MODBUS data interface
Transmission Length ≤ 300 m (0.14 mm²)
≤ 500 m (1.5 mm²)
Supported Protocols patent

Product Size
width 22.5mm
height 102mm
depth 128.5mm
Round wire
diameter 9.5mm

environmental conditions
protection level IP20
ambient temperature (operation) -20°C ... 70°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation ≤ 2000 m
Allowable humidity (operating) ≤ 95% (non-condensing)
2903242

Phoenix SCK-M-I-4S-20A-PV string monitoring module 2903242

Product Center

PRODUCT CENTER