Phoenix SCK-M-U-1500V-PV string monitoring module 2903591,SCK measurement module, used to monitor photovoltaic systems, 1 x voltage measurement (up to 1500V DC),1 x analog output (2 ... 10V)

Product Type voltage transmitter
Product Series SOLARCHECK
insulation characteristics
pollution level 2

protection circuit surge protection; 33V suppressor diode
Power
Rated supply voltage 24V DC-10%... + 25% (or by SSCK-M-I-8S-20A)
Supply Voltage Range 21.6V DC ... 30V DC
Current self-loss 8 mA (typical)
65 mA (max)

measurement
Input Number 1
Input Voltage Range 0V DC ... 1500V DC (CAT III)
0V DC ... 1000V DC (UL)
input voltage 2x 20 MΩ
Connection Mode screw connection
impact waveform DC voltage
temperature coefficient, typical < 0.01 %/K
Maximum transmission error ± 1% (after additional tuning (for 100 - 1500V DC))

signals: analog
voltage output signal 2V DC ... 10V DC
load 10 kΩ
Cable Type stranded wire, shielded

Connection Mode screw connection
stripping length 8mm
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG 24 ... 12
Tightening torque 0.5 Nm ... 0.6 Nm

width 22.5mm
height 102mm
depth 128.5mm

environmental conditions
protection level IP20
Ambient temperature (operation) -20°C ... 70°C
ambient temperature (storage/transport) -40°C ... 85°C
elevation ≤ 2000 m
Allowable humidity (operating) ≤ 95% (non-condensing)
2901674

Phoenix SCK-M-U-1500V-PV string monitoring module 2903591

Product Center

PRODUCT CENTER