Phoenix PT 2 1-S-48DC/FM-3 surge protection equipment 2817958, rail-mounted surge protector, used for surge protection of terminal equipment, plug can send out fault signals, base with signal contacts, pluggable. Working voltage: 48V DC

Product Type Equipment Protection
product series PLUGTRAB PT
IEC power supply system DC
type DIN rail module, split, detachable
Surge protection fault alarm visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category III
pollution level 2
can test protectors using the CHECKMASTER software tests:
IEC Category III
T3
EN Type T3
Ports One

indicator/remote signaling
Connection Name Remote alarm contact
switching function normally closed contact
Nominal operating voltage 7V DC ... 70V DC (open collector)
working current 5 mA DC ... 15 mA (open collector)

Connection Mode screw connection
thread M3
Tightening torque 0.8 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.7mm
height 90mm
depth 65.5mm (7.5mm with DIN rail)
Horizontal stitch pitch 1 Partition

color black (RAL 9005)
flame retardant rating, according to UL 94 V-0
material 600
insulation material PA 6.6
Shell Material PA 6.6

protection channel L-N
L-PE
N-PE
(L ) - (L-)
(L /L-) - PE
movement direction 1L-N & N-PE
Rated voltage UN 48V DC
Maximum continuous operating voltage UC 60V DC
Rated load current IL 26 A (30 °C)
Residual Flow IPE ≤ 10 µA
Nominal discharge current In(8/20)µs 500 A
Combined surge UOC 1 kV (2 Ω)
1 kV (2 Ω)
voltage protection level Up ≤ 120V
response time tA(L-N) ≤ 1 ns
response time tA(L-PEN) ≤ 1 ns
Rated short-circuit current ISCCR 200 A (UCNo spare fuse)
maximum spare fuse with branch wiring 50 A (gG)
2805460

Phoenix PT 2 1-S-48DC/Class FM-3 Surge Protection Equipment 2817958

Product Center