Phoenix PACT RCP-4000A-1A-D95-current transformer 2904921, the kit includes a 1 A measuring transmitter and a Rogowell coil with signal wire. Roche coil length: 300mm, diameter: 95mm. Signal line length: 3 m. The Rogowell coil may measure the AC current of the bus bar and the power line.
| Product Type | current transformer |
| insulation characteristics | |
| insulation | double insulation |
| Overvoltage Category | III (1000V to neutral) |
| IV (600V to neutral) | |
| pollution level | 2 |
| electrical isolation | reinforced insulation conforming to IEC 61010-1 |
| Typical measurement error | <1% |
| protection circuit | surge protection; 33V suppressor diode |
| temperature coefficient | 0.005 %/K (+10°C ... +70°C, same ambient temperature for both components) |
| 0.07 %/K (-20°C ... +10°C, same ambient temperature for both components) | |
| measuring coil | |
| wire structure signal line | 2x 0.22mm (signal wire (tinned)) |
| 1x 0.22mm (shielded wire (tinned)) | |
| insulation | double insulation |
| Rated insulation voltage | 1000V AC (rms CAT III) |
| 600V AC (rms CAT IV) | |
| Test Voltage | 10.45 kV DC (60 seconds) |
| Accuracy | 0.2 (IEC 61869-10: A1) |
| measuring transmitter | |
| Linearity Error | < 0.5 % (from end of range value) |
| Maximum transmission error | ≤ 0.5 % (from end of range) |
| Frequency Range | 45Hz ... 65Hz |
| < 2 kHz | |
| power consumption | < 190 mA (at 19.2V) |
| Test Voltage | 1.5 kV AC (power/input and output: 50Hz,1 minute) |
| Overview | |
| can be calibrated | No |
| Converter Type | Rogowell coil and 1 A measuring transmitter |
| power supply: measuring transmitter | |
| Rated supply voltage | 24V DC -20 % ... +25% |
| Rated supply voltage range | 19.2V DC ... 30V DC |
| Maximum current consumption | 190 mA |
| power consumption | 4W |
| frequency | |
| Name | measuring coil |
| Frequency measurement range | 40Hz ... 20000Hz |
| signal | |
| signal input (at 50Hz) | 100 mV (1000 A) |
| Curve Type | Sine |
| input impedance | 27 kΩ (minimum measurement range) |
| current transformer | |
| configurable/programmable | via DIP switch |
| Rated power | 1.25 VA |
| Rated primary current Isn | 0 A AC ... 100 A AC |
| 0 A AC ... 250 A AC | |
| 0 A AC ... 400 A AC | |
| 0 A AC ... 630 A AC | |
| 0 A AC ... 1000 A AC | |
| 0 A AC ... 1500 A AC | |
| 0 A AC ... 2000 A AC | |
| 0 A AC ... 4000 A AC | |
| phase angle | < 1 ° |
| can be calibrated | No |
| Converter Type | Rogowell coil and 1 A measuring transmitter |
| signal | |
| Name | measuring coil |
| output signal (at 50Hz) | 100 mV (no load, 1000 A) |
| output voltage (no-load operation) | VOUT= M * dI/dt |
| output voltage (sinusoidal, no-load operation) | 100 mV (VOUT= 2 * & pi; * M * f * I(M = 0.318 μH; example: 50Hz;I = 1000 A)) |
| signal | |
| Name | measuring transmitter |
| current output signal | 0 A AC ... 1 A AC |
| Rated power | 1.25 VA |
| load | 0 Ω ... 1.25 Ω |