Phoenix EIK1-SVN-24P-solid state relay module 2940799, electronic module with switch amplification function, used for inductive proximity switch conforming to NAMUR standard, with sensor signal and fault status indicator
| Product Type | Solid State Relay Module |
| Product Series | DEK |
| Application | NAMUR proximity switch sensor |
| insulation characteristics: electrical clearance and creepage distance | |
| Overvoltage Category | III |
| pollution level | 2 |
| Data Management Status | |
| Last data maintenance date | 02.06.2025 |
| control loop | |
| Rated input voltage UN | 8.2V DC ±10% |
| error indication | Display short circuit and open circuit control status via LED (red) |
| protection circuit | 12V zener diode; 12V zener diode |
| sending frequency | 1 kHz |
| switching point | ≥ 2.1 mA (in ON state) |
| ≤ 1.2 mA (in disconnected state) | |
| 6.3 mA ... 10 mA (in short circuit) | |
| 0 mA ... 0.35 mA (when the wire is disconnected) | |
| switching hysteresis | approx. 0.2 mA |
| internal resistance | approx. 1 kΩ |
| Name | output signal |
| Contact Type | 1 N/O contact |
| Digital Output Design | electronic |
| Rated output voltage | ≤ 100 mV (in ON state) |
| UVN- UR;Disconnect status | |
| limit continuous current | 50 mA |
| Voltage drop at maximum limited continuous current | ≤ 1.5V (UR) |
| protection circuit | 36V Zener diode as freewheeling diode; 36V Zener diode as freewheeling diode |
| input side | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Tightening torque | 0.5 Nm |
| output side | |
| Connection Mode | screw connection |
| stripping length | 8mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Tightening torque | 0.5 Nm |
| width | 6.2mm |
| height | 80mm |
| depth | 56mm |
| environmental conditions | |
| ambient temperature (operation) | -25°C ... 50°C |
| ambient temperature (storage/transport) | -25°C ... 70°C |
| electrical clearance and creepage distance | |
| Standards/Regulations | IEC 60664 |
| EN 61000-6-2 | |
| EN 61000-6-4 | |
| Installation Type | DIN rail mounting |
| Assembly Instructions | no spacing arrangement |
| Installation position | arbitrary |