Phoenix VAL-MB-T1/T 2 600 DC-PV/2 V-FM-1/2 Class 2 lightning protection/surge protector 2906292, lightning protection device/surge protector, used for 2-position insulated grounding 600V DC photovoltaic system, suitable for DIN rail installation, With remote communication contact, temperature monitoring protection element, status information is displayed on the module.

Product Type PV Protector
Product Series VALVETRAB MB
IEC Category PV I / II
PV T1 / T2
EN Type T1 / T2
IEC power supply system DC
type rail mounting module, monolithic
Installation position Indoor
separation device inside
accessibility accessible
Connection Configuration Y Configuration
end of life mode OCFM (Partition Error Behavior)
Surge protection fault alarm visual status indication window and remote alarm contact
insulation characteristics
pollution level 2

indicator/remote signaling
Connection Name Remote alarm contact
switching function changeover contact
Nominal operating voltage 5V AC ... 250V AC
5V DC ... 30V DC
Operating current 5 mA AC ... 1.5 A AC
5 mA DC ... 1 A DC

Connection Mode screw connection
thread M5
Tightening torque 3 Nm
stripping length 16mm
Flexible Wire Cross Section 2.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG 14 ... 2
Remote alarm contact
Connection Mode screw connection
thread M2
Tightening torque 0.25 Nm
stripping length 7mm
Flexible Wire Cross Section 0.14 mm² ... 1.5 mm²
Rigid conductor cross section 0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 28 ... 16

Dimensional drawing
width 71.2mm
height 120mm
depth 65.5mm
Horizontal stitch pitch 4 Zoning

color gray (RAL 7042)
flame retardant rating, according to UL 94 V-0
insulation material PA 6.6
PBT
Shell Material PA 6.6

Mechanical parameters
Open Side Panel No

protection channel (L ) - (L-)
(L ) - PE
(L-) - PE
movement direction (L )-PE & (L-)-PE & (L )-(L-)
Rated load current IL 50 A
Residual Flow IPE ≤ 45 µA DC
≤ 420 µA AC
Standby power consumption PC ≤ 36 mVA
Nominal discharge current In(8/20)µs 20 kA
Maximum discharge current Imax(8/20) µs 40 kA
impulse discharge current (10/350)& micro;s, charging 3.125
impulse discharge current (10/350)& micro;s, specific energy 9.77 kJ/Ω
impulse discharge current (10/350)& micro;s, peak limp 6.25 kA
Total discharge current ITotal(8/20) µs 40 kA
Total discharge current ITotal(10/350) µs 12.5 kA
voltage protection level Up ≤ 2.9 kV
Residual pressure Ures ≤ 2.9 kV (In)
≤ 2.1 kV (at 3 kA)
≤ 2.4 kV (at 6.25 kA)
≤ 2.5 kV (10 kA)
≤ 2.8 kV (15 kA)
≤ 3.6 kV (at 40 kA)
response time tA ≤ 25 ns
2905640

Phoenix VAL-MB-T1/T 2 600 DC-PV/2 V-FM-1/2 Class 2 Lightning Protection/Surge Protector 2906292

Product Center

PRODUCT CENTER