Phoenix CTM 2X1-60DC-Surge Protector-Plug and unplug 2838542, protective plug LSA-PLUS, used for protection of single-sided grounded two-wire signal circuit. Rated voltage: 60V DC

Product Type measurement and control technology
Product Series COMTRAB
IEC Category B2
C1
C2
C3
D1
type LSA-PLUS module
Surge protection fault alarm None
can test protectors using the CHECKMASTER software tests:
insulation characteristics
Overvoltage Category II
pollution level 2

Rated voltage UN 60V DC

Connection Mode can be inserted into COMTRAB-TERMIBLOCK and break/switch terminal strip LSA-PLUS

Dimensional drawing
width 9.4mm
height 21mm
depth 52.4mm

color black (RAL 9005)
COPPER
flame retardant rating, according to UL 94 V-0
Shell Material PA 6.6

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Earth Ground
Maximum continuous operating voltage UC 60V DC
50V AC
Rated current 380 mA AC (25 °C)
150 mA DC (25 °C)
UC, the effective working current IC ≤ 70 µA
Residual Flow IPE ≤ 2 µA
Rated discharge current In(8/20)& micro;s (core-ground) 5 kA
pulse discharge current Iimp(350) & micro;s (core-ground) 1 kA
Total discharge current ITotal(8/20) µs 10 kA
Total discharge current ITotal(10/350) µs 2.5 kA
rated power pulse current lan (1000)& micro;s (core-ground) 100 A
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 160V
Output voltage limit 1 kV/& micro;s (core-ground) static ≤ 160V
Residual voltage ln,(wire-ground) ≤ 95V
Ian(10/1000)& micro; Residual pressure at s (line-ground) ≤ 16V
voltage protection level Up(Line-Ground) ≤ 240V (C2 - 10 kV / 5 kA)
≤ 150V (C3 - 100 A)
voltage protection level Upstatic (core-ground) ≤ 85V (C2 - 10 kV / 5 kA)
≤ 16V (C3 - 100 A)
response time tA (core-ground) ≤ 1 ns
input attenuation AE, asymmetric. Typical 0.3 dB (≤ 500 kHz / 100 Ω)
cutoff frequency fg(3 dB), asymmetric. (PE) in the 100 Ω system Typical 2 MHz
capacitance (core-ground) Typical 1 nF
the resistance of each path 3.3 Ω 20%
Surge protection fault alarm None
Impact resistance (line-ground) B2 - 4 kV / 100 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 1 kA
alternating current carrying capacity (line-ground) 5 A - 1 s
2838513